Positioning, Information, 5 parameters – NORD Drivesystems BU0505 User Manual
Page 137: P560 parameter, saving mode, P700, Present operating status
![background image](/manuals/372732/137/background.png)
5 Parameters
BU 0505 GB-1013
137
P560
Parameter, Saving mode
(Saving mode parameter)
S
0 ... 2
{ 1 }
0 = Only in RAM, changes to the parameter settings are no longer saved on the EEPROM.
All previously saved settings are retained, even if the FI is disconnected from the mains.
1 = RAM and EEPROM, all parameter changes are automatically written to the EEPROM
and remain stored there even if the FI is disconnected from the mains supply.
2 = OFF, no saving in RAM and EEPROM possible (no parameter changes are accepted)
NOTE: If BUS communication is used to implement parameter changes, it must be ensured
that the maximum number of write cycles (100,000 x) in the EEPROM is not
exceeded.
Pos : 324 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ P6xx Posi tionier ung @ 0\ mod_1328170219888_388. doc x @ 12270 @ 5 @ 1
Positioning
The parameter group P6xx is used to set the POSICON positioning control and is included above the
version SK 530E.
A detailed description of these parameters can be found in manual BU 0510. (www.nord.com)
Pos : 325 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ P7xx I nf or mationen @ 0\ mod_1328170311705_388. doc x @ 12293 @ 5 @ 1
Information
Parameter
Setting value / Description / Note
Supervisor
Parameter set
Pos : 326 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P700 – Akt ueller Betriebsz ust and @ 0\ mod_1328170483810_388. doc x @ 12318 @ @ 1
P700
[-01]
...
[-03]
Present operating status
(Present operating status)
0.0 ... 25.4
Display of current messages for the actual operating status of the frequency inverter such as
errors, warnings or the cause of a switch-on block. For details of the messages, see Section
6.Fehler! Verweisquelle konnte nicht gefunden werden.
[-01] = Present fault, shows the currently active (unacknowledged) fault .
[-02] = Present warning, indicates a current warning message .
[-03] = Reason for disabled starting, indicates the reason for an active start disable (Section .
NOTE
SimpleBox/ControlBox: with the SimpleBox or ControlBox only warning messages and errors can
be displayed. Display of the messages is in encoded form. For the description of the codes
(warning/error numbers), please refer to the tables in Sections 6.2.
ParameterBox: with the ParameterBox the messages are displayed in plain text. In addition, the
reason for a possible disabling of starting can also be displayed.
Bus: The display of bus-level error messages is made in decimal integer format. If this value is
divided by 10, the display corresponds to that which is listed in Section 6.2.
Example: Display: 20 → Error number 2.0
Pos : 327 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P701 – Letzt e St örung 1.. .5 @ 0\ mod_1328170536746_388. doc x @ 12341 @ @ 1