5 parameters, P404, Analog input filter – NORD Drivesystems BU0505 User Manual
Page 103
5 Parameters
BU 0505 GB-1013
103
P400 ... P403
P401 = 0
à 0 - 10V limited
0.0V
2.5V
5.0V
10.0V
P105
P104
P402
P403
output
frequency
setpoint
voltage
positive
P401 = 1
à 0 - 10V not limited
0.0V
2.5V
5.0V
10.0V
P105
P104
P402
P403
output
frequency
setpoint
voltage
positive
negative
Pos : 187 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P404 – Filter Anal ogeing ang [ SK 54xE] @ 0\ mod_1327681301144_388. doc x @ 9326 @ @ 1
P404
[-01]
[-02]
Analog input filter
(analog input filter) )
S
1 ... 400 ms
{ all 100 }
Adjustable digital low-pass filter for the analog signal. Interference peaks are hidden, the reaction
time is extended.
[-01] = Analog input 1: analog input 1, integrated into the FI
[-02] = Analog input 2: analog input 2, integrated into the FI
The filter time for the analog inputs of the optional external IO extension modules is set in the
parameter set for the relevant module (P161).
Pos : 193 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P410 – Mi ni malfr equenz N ebensoll werte @ 0\ mod_1327681617600_388. doc x @ 9464 @ @ 1
P410
Min. freq. a-in 1/2
(Minimum frequency a-in 1/2 (auxiliary setpoint
value))
P
-400.0 ... 400.0 Hz
{ 0.0 }
The minimum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:
Actual frequency PID
Frequency addition
Frequency subtraction
Auxiliary setpoints via BUS
Process controller
Min. frequency above analog setpoint (potentiometer)
Pos : 194 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P411 – M axi malfrequenz N ebens ollwert e @ 0\ mod_1327940087486_388.doc x @ 9490 @ @ 1