2 Assembly and installation
BU 0505 GB-1013
53
Terminal block X7 – Digital I/O
Relevance
SK 540E
SK 545E
√
Terminals X7:
73
74
26
27
5
7
42
40
RS485 +
RS485 -
DIN6
DIN7
DOUT1
DOUT2
VO 15V
GND/0V
Name
Terminal Function
[factory setting]
Data
Description / wiring suggestion
Parameter
73
Data cable RS485
Baud rate
9600…38400Baud
Termination resistance
R=120
W
BUS connection parallel to RS485 on
RJ12 plug
NOTE: The termination resistance of
DIP switch 1 (see RJ12/RJ45) can also
be used for terminal 73/74.
P503
P509
74
26
Digital input 6
[no function]
7.5...30V, R
i
=3.3k
W
As described for terminal block X5, DIN1
to DIN5.
Not suitable for the evaluation of a motor
thermistor.
P420 [-06]
27
Digital input 7
[no function]
P420 [-07]
Alternatively:
Output 5 (DOUT3)
[no function] Digital output
15V, max. 20mA
For inductive loads:
provide protection with a
free-wheeling diode.
The digital input (DIN7) can also be used
as a digital output (DOUT3).
If P434 [-05] and P420 [-07] are
parameterised with functions, a High
signal of the DOUT function results in a
High signal for the DIN function.
P434 [-05]
5
Output 3 (DOUT1)
[no function]
For evaluation in a control system. The
scope of functions corresponds to that of
the relay (P434).
P434 [-03]
7
Output 4 (DOUT2)
[no function]
P434 [-04]
Alternatively:
Digital input 8
[no function] 7.5...30V, R
i
=3.3k
W
The digital output (DOUT2) can also be
used as a digital input (DIN3).
If P434 [-04] and P420 [-10] are
parameterised with functions, a High
signal of the DOUT function results in a
High signal for the DIN function.
P420 [-10]
42
15V output power
supply
15V
± 20%
Voltage supply for connection to the
digital inputs or the supply of a 10-30V
encoder
40
Reference potential
for digital signals
0V digital