beautypg.com

Terminal block x7 – digital i/o, 2 assembly and installation – NORD Drivesystems BU0505 User Manual

Page 53

background image

2 Assembly and installation

BU 0505 GB-1013

53

Terminal block X7 – Digital I/O

Relevance

SK 540E

SK 545E

Terminals X7:

73

74

26

27

5

7

42

40

RS485 +

RS485 -

DIN6

DIN7

DOUT1

DOUT2

VO 15V

GND/0V

Name

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

73

Data cable RS485

Baud rate
9600…38400Baud

Termination resistance
R=120

W

BUS connection parallel to RS485 on
RJ12 plug

NOTE: The termination resistance of
DIP switch 1 (see RJ12/RJ45) can also
be used for terminal 73/74.

P503
P509

74

26

Digital input 6

[no function]

7.5...30V, R

i

=3.3k

W

As described for terminal block X5, DIN1
to DIN5.

Not suitable for the evaluation of a motor
thermistor.

P420 [-06]

27

Digital input 7

[no function]

P420 [-07]

Alternatively:

Output 5 (DOUT3)

[no function] Digital output

15V, max. 20mA

For inductive loads:
provide protection with a
free-wheeling diode.

The digital input (DIN7) can also be used
as a digital output (DOUT3).

If P434 [-05] and P420 [-07] are
parameterised with functions, a High
signal of the DOUT function results in a
High signal for the DIN function.

P434 [-05]

5

Output 3 (DOUT1)

[no function]

For evaluation in a control system. The
scope of functions corresponds to that of
the relay (P434).

P434 [-03]

7

Output 4 (DOUT2)

[no function]

P434 [-04]

Alternatively:

Digital input 8

[no function] 7.5...30V, R

i

=3.3k

W

The digital output (DOUT2) can also be
used as a digital input (DIN3).

If P434 [-04] and P420 [-10] are
parameterised with functions, a High
signal of the DOUT function results in a
High signal for the DIN function.

P420 [-10]

42

15V output power
supply

15V

± 20%

Voltage supply for connection to the
digital inputs or the supply of a 10-30V
encoder

40

Reference potential
for digital signals

0V digital