NORD Drivesystems BU0505 User Manual
Page 174
SK 54xE – Users Manual for Frequency Inverters
174
BU 0505 GB-1013
The upper limiting values for the various pulse frequencies can be obtained from the following tables.
In all cases, the value (0.1…1.9) which can be set in parameter P537, is limited to the value stated in
the tables according to the pulse frequency. Values below the limit can be set as required.
230V devices: Reduced overload capacity (approx.) due to pulse frequency (P504) and output frequency
Pulse frequency [kHz]
Output frequency [Hz]
4.5
3.0
2.0
1.5
1.0
0.5
0
3...8
200%
170%
150%
140%
130%
120%
110%
10
180%
153%
135%
126%
117%
108%
100%
12
160%
136%
120%
112%
104%
96%
95%
14
150%
127%
112%
105%
97%
90%
90%
16
140%
119%
105%
98%
91%
84%
85%
400V devices: Reduced overload capacity (approx.) due to pulse frequency (P504) and output frequency
Pulse frequency [kHz]
Output frequency [Hz]
4.5
3.0
2.0
1.5
1.0
0.5
0
3...6
200%
170%
150%
140%
130%
120%
110%
8
165%
140%
123%
115%
107%
99%
90%
10
150%
127%
112%
105%
97%
90%
82%
12
130%
110%
97%
91%
84%
78%
71%
14
115%
97%
86%
80%
74%
69%
63%
16
100%
85%
75%
70%
65%
60%
55%
Table 36: Overcurrent relative to pulse and output frequency