BU 0505 GB-1013
Switch-on block messages
Display in the
SimpleBox /
ControlBox
Reason:
Text in the ParameterBox
Cause
•
Remedy
Group
Details in
P700 [-03]
Pos : 430 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 000 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457775195_388.doc x @ 47347 @ @ 1
I000
0.1
Disable voltage from IO
If the function "disable voltage"is parameterised, input (P420
/ P480) is at Low
•
Set "input high"
•
Check signal cable (broken cable)
0.2
IO fast stop
If the function "fast stop"is parameterised, input (P420 /
P480) is at Low
•
Set "input high"
• Check signal cable (broken cable)
0.3
Disable voltage from bus
•
For bus operation (P509):
control word Bit 1 "Low"
0.4
Bus fast stop
• For bus operation (P509):
control word Bit 2 "Low"
0.5
Enable on start
Enable signal (control word, Dig I/O or Bus I/O) was already
applied during the initialisation phase (after mains "ON", or
control voltage "ON").
•
Only issue enable signal after completion of
initialisation (i.e. when the FI is ready)
•
Activation of "Automatic Start" (P428)
Pos : 431 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 006 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457929759_388.doc x @ 47372 @ @ 1
I006
6.0
Charging error
Charging relay not energised, because:
•
Mains / link voltage too low
•
Mains failure
•
Evacuation run activated ((P420) / (P480))
Pos : 432 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 011 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457936856_388.doc x @ 47397 @ @ 1
I011
11.0
Analog Stop
If an analog input of the frequency inverter or a connected
IO extension is configured to detect cable breaks (2-10V
signal or 4-20mA signal), the frequency inverter switches to
the status "Not ready for switch-on" if the analog signal
undershoots the value 1V or 2mA
This also occurs if the relevant analog input is
parameterised to function "0" ("no function").
• Check connections
Pos : 433 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 014 "res er viert" [SK 180E . .. SK 5xxE] @ 2\ mod_1347457944329_388.doc x @ 47422 @ @ 1
I014
14.4
Reserved
Error message for POSICON
à see supplementary
instructions
Pos : 434 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 018 "res er viert" [SK 2xxE/I nf or mation I 018 "res er viert" [SK 2xxE/ SK 5xxE] @ 2\ mod_1347457946544_388.doc x @ 47447 @ @ 1
I018
18.0
Reserved
Information message for "Safe Stop" function
à see
supplementary instructions
Pos : 435 /Anleit ungen/7. / 8. Technisc he Daten [BU 0500/ BU 0200] /7. T echnisc he Daten @ 0\ mod_1328183045569_388. doc x @ 13960 @ 1 @ 1