beautypg.com

Switch-on block messages – NORD Drivesystems BU0505 User Manual

Page 156

background image

SK 54xE – Users Manual for Frequency Inverters

156

BU 0505 GB-1013

Switch-on block messages

Display in the

SimpleBox /
ControlBox

Reason:

Text in the ParameterBox

Cause

Remedy

Group

Details in
P700 [-03]

Pos : 430 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 000 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457775195_388.doc x @ 47347 @ @ 1

I000

0.1

Disable voltage from IO

If the function "disable voltage"is parameterised, input (P420
/ P480) is at Low

Set "input high"

Check signal cable (broken cable)

0.2

IO fast stop

If the function "fast stop"is parameterised, input (P420 /
P480) is at Low

Set "input high"

• Check signal cable (broken cable)

0.3

Disable voltage from bus

For bus operation (P509):

control word Bit 1 "Low"

0.4

Bus fast stop

• For bus operation (P509):

control word Bit 2 "Low"

0.5

Enable on start

Enable signal (control word, Dig I/O or Bus I/O) was already
applied during the initialisation phase (after mains "ON", or
control voltage "ON").

Only issue enable signal after completion of

initialisation (i.e. when the FI is ready)

Activation of "Automatic Start" (P428)

Pos : 431 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 006 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457929759_388.doc x @ 47372 @ @ 1

I006

6.0

Charging error

Charging relay not energised, because:

Mains / link voltage too low

Mains failure

Evacuation run activated ((P420) / (P480))

Pos : 432 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 011 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457936856_388.doc x @ 47397 @ @ 1

I011

11.0

Analog Stop

If an analog input of the frequency inverter or a connected
IO extension is configured to detect cable breaks (2-10V
signal or 4-20mA signal), the frequency inverter switches to
the status "Not ready for switch-on" if the analog signal
undershoots the value 1V or 2mA

This also occurs if the relevant analog input is
parameterised to function "0" ("no function").

• Check connections

Pos : 433 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 014 "res er viert" [SK 180E . .. SK 5xxE] @ 2\ mod_1347457944329_388.doc x @ 47422 @ @ 1

I014

14.4

Reserved

Error message for POSICON

à see supplementary

instructions

Pos : 434 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/I nf or mation I 018 "res er viert" [SK 2xxE/I nf or mation I 018 "res er viert" [SK 2xxE/ SK 5xxE] @ 2\ mod_1347457946544_388.doc x @ 47447 @ @ 1

I018

18.0

Reserved

Information message for "Safe Stop" function

à see

supplementary instructions

Pos : 435 /Anleit ungen/7. / 8. Technisc he Daten [BU 0500/ BU 0200] /7. T echnisc he Daten @ 0\ mod_1328183045569_388. doc x @ 13960 @ 1 @ 1