5 Parameters
BU 0505 GB-1013
105
P416
Ramp time PI setpoint
(Ramp time PI setpoint value)
S
P
0.00 ... 99.99s
{ 2.00 }
This parameter is only effective when the function PID actual frequency is selected.
Ramp for PI setpoint
Fig.: Flow diagram for PID controller
Pos : 201 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P417 – Of fset Analog ausg ang [SK 54xE] @ 0\ mod_1327940454544_388. doc x @ 9651 @ @ 1
P417
[-01]
...
[-03]
Analog output offset
(Analog output offset)
S
P
-10.0 ... 10.0 V
{ all 0.0 }
[-01] = Analog output: analog output integrated into the FI
[-02] = First IOE, "External analog output of first IOE": Analog output 1 of the first IO
extension
[-03] = Second IOE, "External analog output of second IOE": Analog output 1 of the second
IO extension
In the analog output function an offset can be entered to simplify the processing of the analog
signal in other equipment.
If the analog output has been programmed with a digital function, then the difference between the
switch-on point and the switch-off point can be set in this parameter (hysteresis).
Pos : 203 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P418 – Funkti on Analogausgang [ SK 54xE] @ 0\ mod_1327940583880_388. doc x @ 9697 @ @ 1
PID controller
P413 (P-component)
P414 ( I-component)
P415 (D-component)
Frequency ramp
P102, P103
Ramp setpoint
P416
Maximum frequency P105
(monitored, limited)
Maximum frequency P105
(unlimited)
Minimum frequency P104
(monitored, limited)
- Maximum frequency P105
(unlimited)
Maximum
frequency P105
Minimum
frequency P104
Maximum frequency
auxiliary setpoint P410
Minimum frequency
auxiliary setpoint P411
Analog input 1
Analog input 2
Bus setpoint 3
Bus setpoint 2
Auxiliary
setpoint sources
PotentiometerBox
P400-P404
Scaling
P405-P409
Scaling
Analog input 1
Analog input 2
Bus setpoint 1,2,3
Main
setpoint sources
Fixed frequency 1-5
Controlbox /
PotentiometerBox
Jog frequency
P400-P404
Scaling
P405-P409
Scaling
Also in
combination, se e
se tpoint adjustme nt