beautypg.com

Terminal block x5 – digital in – NORD Drivesystems BU0505 User Manual

Page 50

background image

SK 54xE – Users Manual for Frequency Inverters

50

BU 0505 GB-1013

Terminal block X5 – Digital In

Relevance

SK 540E

SK 545E

Terminals X5:

21

22

23

24

39

38

42

40

DIN1

DIN2

DIN3

DIN4

TF-

TF+

VO 15V

GND/0V

Name

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

21

Digital input 1

[ON right]

7.5...30V, R

i

=6.1k

W

Not suitable for thermistor
evaluation.

HTL encoders can only be
connected to DIN2 and
DIN4

Limiting frequencies:
max.

10 kHz

min.

15 Hz

Each digital input has a reaction time of

≤ 5ms.
Connection with internal 15V:

21

22

23

24

39
38

42

40

motor - PTC

15V

Connection with external 7,5-30V:

21

22

23

24

39
38

42

40

motor - PTC

GND / 0V

7.5 … 30V

P420 [-01]

22

Digital input 2

[ON left]

P420 [-02]

23

Digital input 3

[parameter set bit0]

P420 [-03]

24

Digital input 4

[Fixed frequency 1,

P429]

P420 [-04]

39

Thermistor input -

potential isolated
thermistor input, which
cannot be disabled, for
monitoring the motor
temperature with a PTC

38

Thermistor input +

42

15V output power
supply

15V

± 20%

Supply voltage provided by the
frequency inverter for connection to the
digital inputs or the supply of a 10-30V
encoder.

40

Reference potential
for digital signals

0V digital

Reference potential