beautypg.com

8 output choke sk co1, Output choke sk co1 – NORD Drivesystems BU0505 User Manual

Page 34

background image

SK 54xE – Users Manual for Frequency Inverters

34

BU 0505 GB-1013

Inverter ID

NORD

SK 500E

Input choke 3 x 380 - 480 V

L1

W1

D

Detail: Mounting

C

o

n

n

e

c

ti

o

n

Type

Continuous

current

Inductance

L2

B2

Ins

ta

ll

a

tion

0.55 ... 2.2 kW

SK CI1-480/6-C

Part. No.: 276993006

6 A

3 x 4.88 mH

96

60

117

71

45

M4

4

3.0 ... 4.0 kW

SK CI1-480/11-C

Part. No.: 276993011

11 A

3 x 2.93 mH 120

85

140

105

70

M4

4

5.5 ... 7.5 kW

SK CI1-480/20-C

Part. No.: 276993020

20 A

3 x 1.47 mH 155

110

177

135

95

M5

10

11 ... 15 kW

SK CI1-480/40-C

Part. No.: 276993040

40 A

3 x 0.73 mH 155

115

172

135

95

M5

10

18 ... 30hp

SK CI1-480/70-C

Part. No.: 276993070

70 A

3 x 0.47 mH 185

122

220

170

77

M6

35

37 … 45 kW SK CI1-480/100-C

Part. No.: 276993100

100 A

3 x 0.29 mH 240

148

263

180

122

M6

35

55 … 75 kW SK CI1-480/160-C

Part. No.: 276993160

160 A

3 x 0.18 mH 352

140

268

240

105

M8

M8*

90 kW SK CI1-480/280-C

Part. No.: 276993280

280 A

3 x 0.10 mH 352

169

268

240

133 M10 M16*

All dimensions in [mm]

[mm

2

]

* Bolt for copper rail

Table 11: Mains choke data for SK CI1-..., 3~ 480 V

Pos : 41 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 8 Ausgangsdr ossel SK C O1 [BU 0500, u.A.] @ 0\ mod_1325863040983_388. doc x @ 5963 @ 2 @ 1

2.8 Output choke SK CO1

To reduce interference signals from the
motor cable or to compensate for cable
capacitance in long motor cables, an
additional output choke can be installed
into the inverter output.

During installation take care that the pulse
frequency of the frequency inverter is set
to 3 - 6 kHz (P504 = 3 - 6).

These chokes are specified for a
maximum supply voltage of 480 V at
0 - 100 Hz.

An output choke should be fitted for cable lengths over 100 m/30 m (unshielded/shielded). All chokes

have a protection class corresponding to

IP00. The choke used must therefore be installed in a control

cabinet.

D

L2

L1

W1

B2

U

V

V2

U2

W

W3

Similar to