beautypg.com

5 parameters, P000 operating display, P001 selection of disp.value – NORD Drivesystems BU0505 User Manual

Page 77

background image

5 Parameters

BU 0505 GB-1013

77

Parameter
{factory setting}

Setting value / Description / Note

Supervisor

Parameter
set

Pos : 98 /Anl eitungen/ 5. /6. Par ametrierung [ BU 0500 / BU 0200] /Paramet er/P000- P099/Paramet er P000 – Betri ebs anzeig e @ 0\ mod_1327573548773_388.doc x @ 7362 @ @ 1

P000

Operating display

(Operating parameter display)

0.01 ... 9999

In ParameterBoxes with 7-segment displays (e.g. SimpleBox) the operating value which is selected
in P001 is displayed online.

Important information about the operating status of the drive can be read out as required.

Pos : 99 /Anl eitungen/ 5. /6. Par ametrierung [ BU 0500 / BU 0200] /Paramet er/P000- P099/Paramet er P001 – Aus wahl Anz eige @ 0\ mod_1327573728068_388.doc x @ 7386 @ @ 1

P001

Selection of disp.value

(Selection of display value)

0 ... 65

{ 0 }

Selection of the operating display of a ParameterBox with 7-segment display (e.g.: SimpleBox)

0 =

Actual frequency [Hz]:

Actually supplied output frequency

1 =

Speed [rpm]

Calculated actual speed

2 =

Setpoint frequency [Hz]:

Output frequency equivalent to the actual setpoint. This need not
match the actual output frequency.

3 =

Current [A]

Actual, measured output current

4 =

Torque current [A]:

Output current which causes torque

5 =

Voltage [V AC]:

The Actual AC voltage delivered to the output of the FI

6 =

DC link voltage [V DC]

The "Link voltage" is the internal DC voltage of the FI. Amongst
other things, this depends on the level of the mains voltage.

7 =

cos phi

Actual calculated value of the power factor

8 =

Apparent power [kVA]

Actual calculated apparent power

9 =

Effective power [kW]

Actual calculated effective power

10 =

Torque [%]

Actual calculated torque

11 =

Field [%]

Actual calculated field in the motor

12 =

Hours of operation [h]:

Time for which the FI has been connected to mains voltage

13 =

Operating time enable [h]

"Operating time enable" is the time for which the FI was enabled.

14 =

Analog input 1 [%]:

actual value present at analog input 1 of the FI.

15 =

Analog input 2 [%]:

actual value present at analog input 2 of the FI.

16 =

… 18

reserved for Posicon

19 =

Heat sink temperature
[°C]:

actual temperature of the FI heat sink.

20 =

Actual utilisation of motor
[%]

average motor load, based on the known motor data (P201...P209).

21 =

Actual utilisation of brake
resistor [%]

"Utilisation of brake resistor" is the average braking resistor load,
based on the known resistance data (P556...P557).

22 =

Internal temperature [°C]

Actual internal temperature of the FI (SK 54xE / SK 2xxE)

23 =

Motor temperature

Measured via KTY-84

24 =

… 29

reserved for Posicon

30 =

Actual Setpoint MP-S [Hz]

"Actual setpoint of motor parameter function with saving":
(P420…=71/72). The nominal value can be read out with this
function or pre-set (without the drive running).

31 =

… 59

reserved for POSICON or PLC

60 =

R stator ident:

the stator resistance determined by measurement (P220)

61 =

R rotor ident:

the rotor resistance determined by measurement ((P220) Function 2)

62 =

L stray stator ident:

the stray inductance determined by measurement ((P220) Function
2)

63 =

L stator ident:

the inductance determined by measurement ((P220) Function 2)

65 =

Reserved

Pos : 100 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P000-P099/ Paramet er P002 – Dis pl ay-Faktor @ 0\ mod_1327573818457_388. doc x @ 7409 @ @ 1