Mains filter SK HLD (above size 5)

In addition, a chassis mains filter is available for inverters of size V and above. This
enables Class Bradio interference suppression up to a maximum motor cable length
of 25 m.

When connecting the line filter, comply with "Wiring guidelines" Section 0and "EMC"
Section Fehler! Verweisquelle konnte nicht gefunden werden.. In particular, care
must be taken that the pulse frequency is set to the default value (P504 = 6kHz). The
line filter should be placed as close to the side of the inverter as possible.

The connection is by means of screw connections on the upper (mains) and lower
(inverter) ends of the filter

Inverter ID

Filter type

[-V/A]

L1

W1

D

Detail: Mounting

Connection

cross-

section

L2

B2

SK 5xxE

-

551

-

323

-

A

SK HLD 110-500/30

270

55

95

255

30

10

SK 5xxE

-

751

-

323

-

A

SK HLD 110-500/42

310

55

95

295

30

10

SK 5xxE

-

112

-

323

-

A

SK HLD 110-500/75

270

85

135

255

60

35

SK 5xxE

-

152

-

323

-

A

SK 5xxE

-

182

-

323

-

A

SK HLD 110-500/100

270

95

150

255

65

50

SK 5xxE

-

112

-

340

-

A

SK 5xxE

-

152

-

340

-

A

SK HLD 110-500/42

310

55

95

295

30

10

SK 5xxE

-

182

-

340

-

A

SK HLD 110-500/55

250

85

95

235

60

16

SK 5xxE

-

222

-

340

-

A

SK HLD 110-500/75

270

85

135

255

60

35

SK 5xxE

-

302

-

340

-

A

SK 5xxE

-

372

-

340

-

A

SK HLD 110-500/130

270

95

150

255

65

50

SK 5xxE

-

452

-

340

-

A

SK 5xxE

-

552

-

340

-

A

SK HLD 110-500/180

380

130

181

365

102

95

SK 5xxE

-

752

-

340

-

A

SK 5xxE

-

902

-

340

-

A

SK HLD 110-500/250

450

155

220

435

125

150

All dimensions in mm

mm

2

Table 16: Mains filter HLD-...

Pos : 46 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 9 N et zfilt er -Teil 4 - Spannungsbegrenz ungsfilter SK CIF [ BU 0500] @ 0\ mod_1325863390898_388.doc x @ 6009 @ 5 @ 1

Voltage limitation filter SK CIF

Up to and including size 6, the use of a suitable overvoltage filter is mandatory (see also Section 1.5)
in order to comply with cUL requirements. For further information about the overvoltage filter, please
refer to the relevant data sheet. These data sheets can be downloaded from

www.nord.com

.

Inverter ID

Filter type

Part No.

Data sheet

SK 5xxE

-

250

-

323

-

A

-

301

-

323

-

A*

SK CIF-323-20

276997070

TI030 276997070

SK 5xxE

-

401

-

323

-

A

-

112

-

323

-

A*

SK CIF-323-40

276997071

TI030 276997071

SK 5xxE

-

550

-

340

-

A

-

751

-

340

-

A

SK CIF-340-30

276997080

TI030 276997080

SK 5xxE

-

112

-

340

-

A

-

222

-

340

-

A

SK CIF-340-60

276997081

TI030 276997081

* (only with suitable mains choke)

Table 17: Mains filter SK CIF-...

Pos : 47 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 10 Elektrischer Ansc hl uss [ BU 0500] @ 0\ mod_1325863603644_388. doc x @ 6055 @ 2 @ 1

L1 L2

L3

L3'

L2'

L1'

L2

L1

B2

T

Netz / LINE

Gerät / LOAD

B1