Wiring recommendations, 8 additional information – NORD Drivesystems BU0505 User Manual
Page 171
8 Additional information
BU 0505 GB-1013
171
Device type
max. cable length, shielded
Jumper position / DIP:
“EMC-Filter”
see Section 2.10.2
Conducted emissions
150kHz – 30MHz
Class A 1 (C2)
Class B 1 (C1)
SK 5xxE-250-323-A … SK 5xxE-401-323-A
3 – 2
20 m
5 m
3 – 3
5 m
-
SK 5x5E-551-323-A … SK 5x5E-182-323-A
4 – 2
20 m
-
SK 5xxE-550-340-A … SK 5xxE-751-340-A
3 – 2
20 m
5 m
3 – 3
5 m
-
SK 5x5E-112-340-A … SK 5x5E-372-340-A
4 – 2
20 m
-
SK 5x5E-452-340-A … SK 5x5E-902-340-A
DIP: ON
20 m
-
Overview of the standards, which according to product standard EN 61800-3 are applicable as testing
and measuring methods for electric drives whose speed can be altered:
Emission of interference
Emission from cables
(interference voltage)
EN 55011
A 1 or C2
B 1 or C1
Radiated emissions
(Interference field strength)
EN 55011
A 1 or C2
-
Interference immunity EN 61000-6-1, EN 61000-6-2
ESD, discharge of static electricity
EN 61000-4-2
6kV (CD), 8kV (AD)
EMF, high frequency electro-
magnetic fields
EN 61000-4-3
10V/m; 80 - 1000MHz
Burst on control cables
EN 61000-4-4
1kV
Burst on mains and motor cables
EN 61000-4-4
2kV
Surge (phase-phase / phase-ground)
EN 61000-4-5
1kV / 2kV
Cable-led interference due to high
frequency fields
EN 61000-4-6
10V, 0.15 - 80MHz
Voltage fluctuations and drops
EN 61000-2-1
+10%, -15%; 90%
Voltage asymmetries and frequency
changes
EN 61000-2-4
3%; 2%
Table 34: Overview of standards according to product standard EN 61800-3
Wiring recommendations
M
3 ~
PE
L
1
W
V
U
W
V
U
200-240V
or
380-480V
50-60Hz
L
1
L
2
PE
L
2
/N
L
3
L
3
PE
B-
B+
SK 5xxE
Shield angle
Braking resistor
(Accessories)