P201 nominal motor frequency, P202 nominal speed, P203 nominal current – NORD Drivesystems BU0505 User Manual
Page 86: P204 nominal voltage
SK 54xE – Users Manual for Frequency Inverters
86
BU 0505 GB-1013
P201
Nominal motor frequency
(Nominal motor frequency)
S
P
10.0 ... 399.9 Hz
The motor nominal frequency determines the V/f break point at which the FI supplies the nominal
P202
Nominal speed
(Nominal motor speed)
S
P
150 ... 24000 rpm
{
***
}
The nominal motor speed is important for the correct calculation and control of the motor slip and
the speed display (P001 = 1).
Pos : 123 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P203 – M ot or N ennstr om @ 0\ mod_1327588500455_388.doc x @ 7930 @ @ 1
P203
Nominal current
(Nominal motor current)
S
P
0.1 ... 1000.0 A
{
***
}
The nominal motor current is a decisive parameter for the current vector control.
Pos : 124 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P204 – M ot or N enns pannung @ 0\ mod_1327588687111_388.doc x @ 7953 @ @ 1
P204
Nominal voltage
(Nominal motor voltage)
S
P
100 ... 800 V
{
***
}
The >Nominal voltage< matches the mains voltage to the motor voltage. In combination with the
nominal frequency, the voltage/frequency characteristic curve is produced.
Pos : 125 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P200-P299/ Paramet er P205 – M ot or N ennleis tung @ 0\ mod_1327588736705_388.doc x @ 7976 @ @ 1
*** These settings are dependent on the nominal power of the FI or the selection in parameter P200.