5 parameters – NORD Drivesystems BU0505 User Manual
Page 109
5 Parameters
BU 0505 GB-1013
109
Value Function
Description
Signal
13
PTC input
2
Analog evaluation of signal present. Switching threshold approx. 2.5 V,
Switch-off delay = 2 sec, warning after 1 sec.
NOTE: Fnct. 13 can only be used via DIN 5 up to SK 535E, sizes 1 - 4!
For SK 54xE and sizes above Size 5, there is a separate connection which
cannot be deactivated. If the motor is equipped with a thermistor, for these
devices both terminals must be bridged in order to deactivate the function
(status as delivered).
level
14
Remote control
2, 4
With Bus system control, low level switches the control to control via control
terminals.
High
15
Jog frequency
1
The fixed frequency value can be adjusted using the HIGHER/LOWER and
ENTER keys (P113), if control is via the ControlBox or ParameterBox.
High
16
Motor potentiometer
As in setting 09, however, the frequency is not maintained below the minimum
frequency P104 and above the maximum frequency P105.
Low
17
Para. Set Switchovr. 2
Second Bit of the parameter set switch over, selection of the active parameter
set 1…4 (P100).
High
18
Watchdog
2
Input must see a High flank cyclically (P460), otherwise error E012 will cause a
shutdown. Function starts with the 1st high flank.
0
à1
Flank
19
Setpoint 1 on/off
Analog input switch-on and switch-off 1/2 (high = ON) The low signal sets the
analog input to 0 % which does not lead to shutdown when the minimum
frequency (P104) > than the absolute minimum frequency (P505).
High
20
Setpoint 2 on/off
21
Fixed frequency 5
1
The frequency from P433 is added to the actual setpoint value.
High
22
... 25
reserved POSICON (BU 0510)
26
... 29 impulse functions:
Description below:
30
Disable PID
Switching the PID controller / process controller function on and off (high = ON)
High
31
Disable right running
2
Blocks the >Enable right/left< via a digital Input or bus control. Does not depend
on the actual direction of rotation of the motor (e.g. following negated setpoint).
Low
32
Disable left running
2
Low
33
... 42 impulse functions:
Description below (only SK 500E … 535E).
43
... 44 Speed measurement
with HTL encoder
Description below:
44
3-Wire Direction
(Direction reversal button)
3-Wire-Control, this control function provides an alternative to enable R/L (01,
02), in which a permanently applied level is required.
Here, only a control impulse is required to trigger the function. Control of the FI
can therefore be performed entirely with buttons.
A pulse on the function "Reverse direction of rotation" inverts the present
direction of rotation. This function is reset with a "Stop signal" or by activating a
button for the functions 45, 46, 49.
0
à1
Flank
45
3-W-Ctrl.Start-Right
(Closing button)
0
à1
Flank
46
3-W-Ctrl.Start-Left
(Closing button)
0
à1
Flank
49
3-Wire-Ctrl.Stop
(Opening button)
1
à0
Flank
47
Motorpot.Freq.+
In combination with enable R/L the output frequency can be continuously
varied. To save a current value in P113, both inputs must be at a High voltage
for 0.5 s. This value then applies as the next starting value for the same
direction of rotation (Enable R/L) otherwise start at f
MIN
. Values from other
setpoint sources (e.g. fixed frequencies) are not taken into account.
High
48
Motorpot.Freq.-
High
50
Bit 0 Fixed. freq.Array
Fixed frequency array, binary coded digital inputs to generate up to 32 fixed
frequencies. (P465: -01...-31)
High
51
Bit 1 Fixed. freq.Array
High
52
Bit 2 Fixed. freq.Array
High
53
Bit 3 Fixed. freq.Array
High
54
Bit 4 Fixed. freq.Array
High
55
… 64
reserved POSICON (BU 0510)
65
… 69
Reserved
70
Evacuation runs
SW 1.7 and above
Only for devices with external 24V control voltage (SK 5x5E). There is therefore
also the possibility of operation with a very low link circuit voltage. With this
function the charging relay is activated and the undervoltage and phase error
detection are deactivated.
CAUTION! There is no overload monitoring! (e.g. lifting gear)
High