7 Technical data
BU 0505 GB-1013
159
7.2.2 Electrical data 230V
FI type (size 1):
SK 5xxE…
-250-323-A
-370-323-A
-550-323-A
-750-323-A
Nominal motor power
(4-pole standard motor)
230V
0.25hp
0.37 kW
0.55 kW
0.75hp
240V
1
/
3
hp
½ hp
¾ hp
1 hp
Input
Mains voltage
1~ /3~ 230V
1 / 3 AC 200 … 240V,
± 10%, 47 … 63Hz
Input current
1~ /3~ rms
3.7 A / 2.4 A
4.8 A / 3.1 A
6.5 A / 4.2 A
8.7 A / 5.6 A
1~ /3~ FLA
3.7 A / 2.4 A
4.8 A / 3.1 A
6.4 A / 4.1 A
8.6 A / 5.5 A
Recommended
mains fuse*
1~ /3~ 1 AC slow-
acting
6 A / 6 A
6 A / 6 A
10 A / 10 A
15 A / 10 A
CB
5 A / 5 A
5 A / 5 A
10 A / 10 A
10 A / 10 A
Permissible mains
fuses for UL*
Fuse, 300V
6 A / 6 A
6 A / 6 A
10 A / 10 A
25 A / 10 A
Bussmann
FRS-R-6
FRS-R-6
FRS-R-10
FRS-R-15 /-10
CB
5 A / 5 A
5 A / 5 A
10 A / 10 A
10 A / 10 A
O
ut
put
Output voltage
3~ 230V
3 AC 0 - Mains voltage
Output current
rms
1.7 A
2.2 A
3.0 A
4.0 A
FLA
1.7 A
2.2 A
2.9 A
3.9 A
Min. braking resistor
Accessories
240
W
190
W
140
W
100
W
Type of ventilation
Free convection
Weight
Approx. [kg]
1.4
* see also Section 1.5.2. Fuses: High-Interrupting Capacity, Current Limiting Classes (z.B. R, J, …), circuit breaker (CB): Inverse Time Trip Type
FI type (size 2/ 3):
SK 5xxE…
-111-323-A
-151-323-A
-221-323-A
-301-323-A
-401-323-A
Nominal motor power
(4-pole standard motor)
230V
1.1 kW
1.5 kW
2.2 kW
3.0 kW
4.0 kW
240V
1½ hp
2 hp
3 hp
4 hp
5 hp
Input
Mains voltage
1~ /3~ 230V
1 / 3 AC
200 … 240V,
± 10%, 47 … 63Hz
3 AC
200 … 240V,
± 10%, 47 … 63Hz
Input current
1~ /3~ rms 12.0 A / 7.7 A 15.2 A / 9.8 A 19.6 A/ 13.3 A
- / 17.5 A
- / 22.4 A
1~ /3~ FLA 11.9 A / 7.6 A 15.0 A / 9.7 A 19.4 A/ 13.1 A
- / 17.2 A
- / 22.0 A
Recommended
mains fuse*
1~ /3~ 1 AC slow-
acting
15 A / 10 A
20 A / 10 A
25 A / 20 A
- / 20 A
- / 25 A
CB
- / 10 A
- / 10 A
- / -
- / 20 A
- / 25 A
Permissible mains
fuses for UL*
Fuse, 300V
30 A / 10 A
30 A / 10 A
30 A / 30 A
- / 30 A
- / 30 A
Bussmann FRS-R-15 /-10 FRS-R-20 /-10 FRS-R-25 /-20
- / FRS-R-20
- / FRS-R-25
CB
- / 10 A
- / 10 A
- / -
- / 25 A
- / 25 A
O
ut
put
Output voltage
3~ 230V
3 AC 0 - Mains voltage
Output current
rms
5.5 A
7.0 A
9.5 A
12.5 A
16.0 A
FLA
5.4 A
6.9 A
9.3 A**
12.3 A
15.7 A
Min. braking resistor
Accessories
75
W
62
W
46
W
35
W
26
W
Type of ventilation
Fan cooling, temperature-controlled Switching thresholds:
ON= 57°C
OFF=47°C
Weight
Approx. [kg]
1.8
2.7
* see also Section 1.5.2. Fuses: High-Interrupting Capacity, Current Limiting Classes (z.B. R, J, …), circuit breaker (CB): Inverse Time Trip Type
** for single-phase mains supply of SK 5xxE
-
221
-
323
-