beautypg.com

5 parameters, P435, Dig. out scaling – NORD Drivesystems BU0505 User Manual

Page 113

background image

5 Parameters

BU 0505 GB-1013

113

Value Function

Description

Signal*

10

Motor overtemperature
warning

Motor overtemperature (warning): The motor temperature is evaluated via the PTC
input or a digital input.

àMotor is too hot. This warning is given immediately,

overheating switch-off after 2 seconds.

Low

11

Torque current limit
active

Torque current limit/Current limit active (warning): The limiting value in P112 or P536
has been reached. A negative value in P435 inverts the reaction. Hysteresis = 10 %.

Low

12

Value of P541

The output can be set using parameter P541 independently of the actual operating
status of the FI.

High

13

Generator torque current
limit

Limit value in P112 was reached in the generator range. Hysteresis = 10 %.

High

14

... 17 Reserved

--

18

FI ready

The FI is ready for operation. After being enabled it delivers an output signal.

High

19

… 29 reserved POSICON (BU 0510)

--

30

BusIO In Bit 0

Control by Bus In Bit 0 (P546 …)

High

31

BusIO In Bit 1

Control by Bus In Bit 1 (P546 …)

High

32

BusIO In Bit 2

Control by Bus In Bit 2 (P546 …)

High

33

BusIO In Bit 3

Control by Bus In Bit 3 (P546 …)

High

34

BusIO In Bit 4

Control by Bus In Bit 4 (P546 …)

High

35

BusIO In Bit 5

Control by Bus In Bit 5 (P546 …)

High

36

BusIO In Bit 6

Control by Bus In Bit 6 (P546 …)

High

37

BusIO In Bit 7

Control by Bus In Bit 7 (P546 …)

High

38

Value from Bus setpoint

Value from bus setpoint (P546 …)

High

Details can be found in the bus manuals

39

STO inactive

The relay / bit deactivates if STO or the Safe Stop are active.

High

40

reserved PLC (BU 0550)

* For relay contacts (High = "Contact closed", Low = "Contact open")

Pos : 231 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter übersc hrift - Forts et zung Tabelle @ 1\ mod_1331566123473_388. doc x @ 18340 @ @ 1

Parameter
{factory setting}

Setting value / Description / Note

Supervisor

Parameter
set

Pos : 233 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P435 – N or mier ung Digit alausgänge [SK 54xE] @ 0\ mod_1328001442849_388. doc x @ 10296 @ @ 1

P435

[-01]

...

[-05]

Dig. out scaling

(Scaling of digital output)

P

-400 ... 400 %

{ all 100 }

Adjustment of the limiting values of the digital functions. For a negative value, the output function
will be output negative.

[-01] = Output 1 / MFR1, relay output 1:

[-02] = Output 2 / MFR2, relay output 2:

[-03] = Output 3 / DOUT1, digital output 1

[-04] = Output 4 / DOUT2, digital output 2

[-05] = Output 5 / DOUT3, digital output 3

Reference to the following values:

Current limit (3) = x [%]

× P203 >Rated motor current<

Torque current limit (4) = x [%]

× P203 × P206 (calculated rated motor torque)

Frequency limit (5) = x [%]

× P201 >Rated motor frequency<

Pos : 235 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P436 – H yst eres e Digit alausgänge [SK 54xE] @ 0\ mod_1328001572366_388. doc x @ 10342 @ @ 1