5 parameters, P435, Dig. out scaling – NORD Drivesystems BU0505 User Manual
Page 113
5 Parameters
BU 0505 GB-1013
113
Value Function
Description
Signal*
10
Motor overtemperature
warning
Motor overtemperature (warning): The motor temperature is evaluated via the PTC
input or a digital input.
àMotor is too hot. This warning is given immediately,
overheating switch-off after 2 seconds.
Low
11
Torque current limit
active
Torque current limit/Current limit active (warning): The limiting value in P112 or P536
has been reached. A negative value in P435 inverts the reaction. Hysteresis = 10 %.
Low
12
Value of P541
The output can be set using parameter P541 independently of the actual operating
status of the FI.
High
13
Generator torque current
limit
Limit value in P112 was reached in the generator range. Hysteresis = 10 %.
High
14
... 17 Reserved
--
18
FI ready
The FI is ready for operation. After being enabled it delivers an output signal.
High
19
… 29 reserved POSICON (BU 0510)
--
30
BusIO In Bit 0
Control by Bus In Bit 0 (P546 …)
High
31
BusIO In Bit 1
Control by Bus In Bit 1 (P546 …)
High
32
BusIO In Bit 2
Control by Bus In Bit 2 (P546 …)
High
33
BusIO In Bit 3
Control by Bus In Bit 3 (P546 …)
High
34
BusIO In Bit 4
Control by Bus In Bit 4 (P546 …)
High
35
BusIO In Bit 5
Control by Bus In Bit 5 (P546 …)
High
36
BusIO In Bit 6
Control by Bus In Bit 6 (P546 …)
High
37
BusIO In Bit 7
Control by Bus In Bit 7 (P546 …)
High
38
Value from Bus setpoint
Value from bus setpoint (P546 …)
High
Details can be found in the bus manuals
39
STO inactive
The relay / bit deactivates if STO or the Safe Stop are active.
High
40
reserved PLC (BU 0550)
* For relay contacts (High = "Contact closed", Low = "Contact open")
Pos : 231 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter übersc hrift - Forts et zung Tabelle @ 1\ mod_1331566123473_388. doc x @ 18340 @ @ 1
Parameter
{factory setting}
Setting value / Description / Note
Supervisor
Parameter
set
Pos : 233 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P435 – N or mier ung Digit alausgänge [SK 54xE] @ 0\ mod_1328001442849_388. doc x @ 10296 @ @ 1
P435
[-01]
...
[-05]
Dig. out scaling
(Scaling of digital output)
P
-400 ... 400 %
{ all 100 }
Adjustment of the limiting values of the digital functions. For a negative value, the output function
will be output negative.
[-01] = Output 1 / MFR1, relay output 1:
[-02] = Output 2 / MFR2, relay output 2:
[-03] = Output 3 / DOUT1, digital output 1
[-04] = Output 4 / DOUT2, digital output 2
[-05] = Output 5 / DOUT3, digital output 3
Reference to the following values:
Current limit (3) = x [%]
× P203 >Rated motor current<
Torque current limit (4) = x [%]
× P203 × P206 (calculated rated motor torque)
Frequency limit (5) = x [%]
× P201 >Rated motor frequency<
Pos : 235 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P436 – H yst eres e Digit alausgänge [SK 54xE] @ 0\ mod_1328001572366_388. doc x @ 10342 @ @ 1