5 Parameters
BU 0505 GB-1013
141
P714
Operating time
(Operating time)
0.10 ... ___ h
This parameter shows the time for which the FI was connected to the mains and was ready for
operation.
Pos : 342 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P715 – Freigabedauer @ 0\ mod_1328172731474_388.doc x @ 12686 @ @ 1
P715
Running time
(Enablement time)
0.00 ... ___ h
This parameter shows the time for which the FI was enabled and supplied current to the output.
Pos : 343 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P716 – Akt uelle Fr equenz @ 0\ mod_1328172775215_388.doc x @ 12709 @ @ 1
P716
Current frequency
(Actual frequency)
-400.0 ... 400.0 Hz
Displays the actual output frequency.
Pos : 344 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P717 – Akt uelle Dr ehzahl @ 0\ mod_1328172889966_388.doc x @ 12732 @ @ 1
P717
Current speed
(Actual rotation speed)
-9999 ... 9999 rpm
Displays the actual motor speed calculated by the FI.
Pos : 345 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P718 – Akt uelle Sollfrequenz @ 0\ mod_1328172931732_388.doc x @ 12755 @ @ 1
P718
[-01]
...
[-03]
Current set freq.
(Actual setpoint frequency)
-400.0 ... 400.0 Hz
Displays the frequency specified by the setpoint. (See also Section 8.1
[-01] = Actual setpoint frequency from the setpoint source
[-02] = Actual setpoint frequency after processing in the FI status machine
[-03] = Actual setpoint frequency after frequency ramp
Pos : 346 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P719 – Akt ueller Strom @ 0\ mod_1328172979998_388. doc x @ 12778 @ @ 1
P719
Actual current
(Actual current)
0.0 ... 999.9 A
Displays the actual output current.
Pos : 347 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P720 – Akt ueller M oments trom @ 0\ mod_1328173025780_388. doc x @ 12801 @ @ 1
P720
Act. torque current
(Actual torque current)
-999.9 ... 999.9 A
Displays the actual calculated torque-developing output current (active current). Basis for
calculation are the motor data P201...P209.
à negative values = generator, à positive values = drive
Pos : 348 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P721 – Akt ueller F eldstrom @ 0\ mod_1328173074624_388. doc x @ 12824 @ @ 1
P721
Actual field current
(Actual field current)
-999.9 ... 999.9 A
Displays the actual calculated field current (reactive current). Basis for calculation are the motor
data P201...P209.