NORD Drivesystems BU0505 User Manual
Page 115
5 Parameters
BU 0505 GB-1013
115
P463
2. Encoder ratio
(2nd encoder speed ratio)
S
0.01 ... 100.0
{ 1.00 }
If the HTL incremental encoder is not mounted directly on the motor shaft, the correct speed ratio
for the motor speed and the encoder speed must be set.
speed
Encoder
speed
Motor
P463
=
Only if P461 = 1, 2, 3 4 or 5, therefore not in Servo mode (motor speed control)
Pos : 249 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P464 – M odus Festfr equenz en @ 0\ mod_1328002346013_388.doc x @ 10664 @ @ 1
P464
Fixed frequencies mode
(Fixed frequencies mode)
S
0 ... 1
{ 0 }
above SW 1.7
This parameter determines the form in which fixed frequencies are to be processed.
0 = Addition to main setpoint: Fixed frequencies and the fixed frequency array are added
to each other. I.e. they are added together, or added to an analog setpoint to which limits
are assigned according to P104 and P105.
1 = Main setpoint: Fixed frequencies are not added - neither together, nor to analog
setpoints.
If for example, a fixed frequency is switched to an existing analog setpoint, the analog
setpoint will no longer be considered.
Programmed frequency addition or subtraction with an analog input value or a bus
setpoint is still possible and valid, as is the addition to the setpoint of a motor
potentiometer function (function of digital inputs: 71/72)
If several fixed frequencies are selected simultaneously, the frequency with the highest
value has priority (E.g.: 20>10 or 20>-30).
Note:
The highest active fixed frequency is added to the setpoint value of the motor
potentiometer if the functions 71 or 72 are selected for 2 digital inputs.
Pos : 250 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P465 – Fes tfreq uenz F el d @ 0\ mod_1328002410529_388.doc x @ 10687 @ @ 1
P465
[-01]
...
[-31]
Fixed freq. Array
(Fixed frequency / Array)
-400.0 ... 400.0 Hz
{ 0.0 }
In the array levels, up to 31 different fixed frequencies can be set, which in turn can be encoded
for the functions 50…54 in binary code for the digital inputs.
Pos : 251 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P466 – Mi ni malfr equenz Pr oz essregl er @ 0\ mod_1328002464186_388. doc x @ 10710 @ @ 1
P466
Min. Freq. Process Controller
(Minimum frequency process controller)
S
P
0.0 ... 400.0 Hz
{ 0.0 }
With the aid of the minimum frequency process controller the control ratio can also be kept to a
minimum ratio, even with a master value of “zero”, in order to enable adjustment of the
compensator. Further details in P400 and Section 8.2.
Pos : 252 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P468 – Dr ehzahlregl. m HTL [SK 54xE] @ 2\ mod_1355751051785_388.doc x @ 52534 @ @ 1