Temperature ranges, P 2 0 1, P 4 0 6 – NORD Drivesystems BU0505 User Manual

Page 74: P 2 0 7, P 2 0 8, P 2 2 0, P 4 0 7, P 4 0 5, P 4 0 8, P 0 0 1

background image

SK 54xE – Users Manual for Frequency Inverters

74

BU 0505 GB-1013

1. Set the motor data P201-

P207 according to the type
plate

2. Determine the motor stator

resistance P208 at 20°C
with P220=1.

3. Analog input 2 function,

P405=48 (Motor
temperature)

4. Analog input 2 mode 2,

P406=1 (taking negative
temperatures into account)

5. Matching of analog input 2:

P407= 1.54 V and
P408= 2.64 V (with R

V

=

2.7

kΩ)

6. Adjust time constants:

P409=400ms (Maximum
value of filter time constant)

7. Motor temperature control:

P001=23 (Temperature
display, operation display SK
TU3-CTR / SK CSX-0)

P 0 - -

Display parameters

to

_ _ _ _

P 1 - -

Basic parameter

P 2 - -

Motor data

P 4 - -

Control terminals

P 5 - -

Additional parameter

P 7 - -

Information

P 2 0 1

Nominal motor frequency

10 … 400Hz

P 4 0 6

Mode analog input 2

P406 = 1 (0...10V)

P 2 0 7

Motor switching

Star/delta

P 2 0 8

Stator resistance

0 … 300

W

P 2 2 0

Parameter identification

P220 1 / 2

P 4 0 7

Adjustment of analog input 2

P407=1.54V

P 4 0 5

Analog input function 2

P405=48 (Motor temperature)

P 4 0 8

Adjustment of analog input 2

P408=2.64V

P 0 0 1

Motor temperature

-50 ... 150°C

P 4 0 9

Analog input filter 2

P409=400ms

Note

Temperature ranges

Excess temperature of the motor is also monitored and at 155°C (switching threshold for the thermistor) causes
the drive unit to shut down with error message E002.

To determine the stator resistance of the motor, the temperature range 15 … 25°C should not be exceeded.

Pos : 94 /Anl eitungen/ 4. Inbetriebnahme [ BU 0500]/ 4. 4 Fr equenz- Additi on und Subtr aktion über Bedi enboxen. @ 0\ mod_1327571806191_388. doc x @ 7290 @ 2 @ 1

4.4 Frequency addition and subtraction via operating boxes

(software version 1.7 and above)

If the parameter P549 (PotentiometerBox Function) is set to 4 “Frequency addition” or 5 “Frequency

subtraction”, a value can be added or subtracted via the value keys

or

with the ControlBox or

the ParameterBox.

If the ENTER key

is confirmed, the value is saved in P113. The next time the device is started, the

value will be added or subtracted immediately.

As soon as the inverter is enabled, the ControlBox switches to the operating display. With the
ParameterBox, a change of value can only be made in the operating display. If the ControlBox is
enabled, parameterisation is no longer possible. Enabling via the ControlBox or ParameterBox is also
no longer possible in this mode, even if P509 = 0 and P510 = 0.

Note:

In order to safely activate the ParameterBox in this mode, the STOP key

must be

pressed once.

Pos : 95 /Anl eitungen/ 5. /6. Par ametrierung [ BU 0500 / BU 0200] /5. Paramet er -1- @ 0\ mod_1327572853172_388. doc x @ 7316 @ 1 @ 1