Table 24: signal details for hiperface encoders, Rotary encoder function test – NORD Drivesystems BU0505 User Manual
Page 62
SK 54xE – Users Manual for Frequency Inverters
62
BU 0505 GB-1013
Function
Signal designation
Signal voltage
Sine reference voltage
Sin Ref
2.5V U
m
Cosine reference voltage
Cos Ref
2.5V U
m
Sine signal
Sin
1V U
ss
Cosine signal
Cos
1V U
ss
Table 24: Signal details for Hiperface encoders
Function
Cable colours, for Hiperface
encoders
Connections for SK 54xE
Terminal block X5, X6 or X14
7-12V supply
red
49 VO 12V
0V supply
blue
40 GND/0V
+ SIN
white
51 ENC A+
REFSIN
brown
52 ENC A-
+COS
pink
53 ENC B+
REFCOS
black
54 ENC B-
Data + (RS485)
grey or yellow
65 DAT +
Data - (RS485)
green or violet
66 DAT-
Cable shield
connected to a large area of the frequency inverter housing or shielding angle
Table 25: Colour and contact assignment for Hiperface encoders
Note
Rotary encoder function test
The voltage difference between the SIN and COS tracks can be measured with the aid of parameter P709 [-09]
and [-10]. If the Hiperface encoder is rotated, the voltage difference should range between approx. -0.5V and
0.5V.
Pos : 83 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 12 RJ 45 WAGO- Anschl uss modul [Allg.] @ 0\ mod_1325866182423_388. doc x @ 6170 @ 2 @ 1
U
ss
U
m