Terminal block x6 – encoder – NORD Drivesystems BU0505 User Manual
Page 52

SK 54xE – Users Manual for Frequency Inverters
52
BU 0505 GB-1013
Terminal block X6 – Encoder
Relevance
SK 540E
SK 545E
√
√
Terminals X6:
49
51
52
53
54
VO 12V
ENC A+
ENC A-
ENC B+
ENC B-
Name
Terminal Function
[factory setting]
Data
Description / wiring suggestion
Parameter
49
12V output power
supply
12V
± 20%
max. 150mA
The incremental encoder input can be
used for the exact regulation of speed of
rotation, additional set point functions or
positioning.
An encoder system with 10-30V supply
voltage must be used in order to
compensate for voltage drop in long
cable connections.
Note: Encoders with 5V supply are not
suitable in order to set up a system
which operates reliably.
51
Track A
TTL, RS422
500…8192Imp./Rpm.
Limiting frequencies:
max.
205 kHz
min.
250 Hz
P300
52
Track A inverse
53
Track B
54
Track B inverse
Pos : 65 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 10. 5 Elektrischer Ansc hluss St euert eil- Klemmenbl oc k X7 – Digital I/O [ SK 54xE] @ 2\ mod_1355475437641_388.doc x @ 52186 @ 5 @ 1