Warning messages – NORD Drivesystems BU0505 User Manual
Page 154
SK 54xE – Users Manual for Frequency Inverters
154
BU 0505 GB-1013
20.8
Program Memory Error
"Program memory error"
(EEPROM error)
20.9
Memory Protection Error
21.0
NMI Error
(not used by hardware)
21.1
PLL Error
21.2
ADU Error "Overrun"
21.3
PMI Error "Access Error"
21.4
Userstack Overflow
Pos : 418 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E022 "res er viert" [ SK 5xxE] @ 2\ mod_1361527702934_388. doc x @ 59091 @ @ 1
E022
---
Reserved
Error message for PLC
à see supplementary instructions
Pos : 419 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E023 "res er viert" [ SK 5xxE] @ 2\ mod_1361527808170_388. doc x @ 59116 @ @ 1
E023
---
Reserved
Error message for PLC
à see supplementary instructions
Pos : 420 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E025 "res er viert" [ SK 54xE] @ 2\ mod_1361529602588_388.doc x @ 59166 @ @ 1
E025
---
Reserved
Error message for POSICON
à see supplementary
instructions
Pos : 421 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ 6./ 7. 2 - Warnmeldungen (Tabellenüberschrif t) @ 3\ mod_1361803463080_388. doc x @ 59898 @ 5 @ 1
Warning messages
Display in the
SimpleBox /
ControlBox
Warning
Text in the ParameterBox
Cause
•
Remedy
Group
Details in
P700 [-02]
Pos : 422 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 001 [SK 180E . .. SK 5xxE] @ 2\ mod_1347456220101_388. doc x @ 46975 @ @ 1
C001
1.0
Overtemp.
Inverter
"Inverter overtemperature"
(inverter heat sink)
Inverter temperature monitoring
Warning: permissible temperature limit reached.
•
Reduce ambient temperature
•
Check the FI fan / control cabinet ventilation
•
Check the FI for dirt
Pos : 423 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 002 [SK 5xxE] @ 2\ mod_1361536747300_388. doc x @ 59221 @ @ 1
C002
2.0
Overtemp. Motor PTC
"Overtemperature motor
thermistor "
Warning from motor temperature sensor (triggering
threshold reached)
•
Reduce motor load
• Increase motor speed
• Use external motor fan
2.1
Overtemp. Motor I²t
"Motor overtemperature I²t"
Only if I
2
t motor (P535) is
programmed.
Warning: I2t- motor monitoring (1.3 times the rated current
reached for the time period specified in (P535))
•
Reduce motor load
• Increase motor speed
Pos : 424 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 003 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457006237_388. doc x @ 47199 @ @ 1
C003
3.0
Overcurrent, I
2
t limit
Warning: Inverter: I
2
t limit has triggered, e.g. > 1.3 x I
n
for
60s (please also note P504)
• Continuous overload at FI output
3.1
Overcurrent, chopper I
2
t
Warning: I
2
t limit for the brake chopper has triggered, 1.3x
value attained for 60s (also note P554, if present, as well as
P555, P556, P557)
• Avoid overload of brake resistance
3.5
Torque current limit
Warning: Torque current limit reached
•
Check
(P112)
3.6
Current limit
Warning: Current limit reached
•
Check
(P536)