beautypg.com

Warning messages – NORD Drivesystems BU0505 User Manual

Page 154

background image

SK 54xE – Users Manual for Frequency Inverters

154

BU 0505 GB-1013

20.8

Program Memory Error

"Program memory error"
(
EEPROM error)

20.9

Memory Protection Error

21.0

NMI Error

(not used by hardware)

21.1

PLL Error

21.2

ADU Error "Overrun"

21.3

PMI Error "Access Error"

21.4

Userstack Overflow

Pos : 418 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E022 "res er viert" [ SK 5xxE] @ 2\ mod_1361527702934_388. doc x @ 59091 @ @ 1

E022

---

Reserved

Error message for PLC

à see supplementary instructions

Pos : 419 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E023 "res er viert" [ SK 5xxE] @ 2\ mod_1361527808170_388. doc x @ 59116 @ @ 1

E023

---

Reserved

Error message for PLC

à see supplementary instructions

Pos : 420 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E025 "res er viert" [ SK 54xE] @ 2\ mod_1361529602588_388.doc x @ 59166 @ @ 1

E025

---

Reserved

Error message for POSICON

à see supplementary

instructions

Pos : 421 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ 6./ 7. 2 - Warnmeldungen (Tabellenüberschrif t) @ 3\ mod_1361803463080_388. doc x @ 59898 @ 5 @ 1

Warning messages

Display in the

SimpleBox /
ControlBox

Warning

Text in the ParameterBox

Cause

Remedy

Group

Details in
P700 [-02]

Pos : 422 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 001 [SK 180E . .. SK 5xxE] @ 2\ mod_1347456220101_388. doc x @ 46975 @ @ 1

C001

1.0

Overtemp.

Inverter

"Inverter overtemperature"

(inverter heat sink)

Inverter temperature monitoring

Warning: permissible temperature limit reached.

Reduce ambient temperature

Check the FI fan / control cabinet ventilation

Check the FI for dirt

Pos : 423 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 002 [SK 5xxE] @ 2\ mod_1361536747300_388. doc x @ 59221 @ @ 1

C002

2.0

Overtemp. Motor PTC

"Overtemperature motor
thermistor "

Warning from motor temperature sensor (triggering
threshold reached)

Reduce motor load

• Increase motor speed

• Use external motor fan

2.1

Overtemp. Motor I²t

"Motor overtemperature I²t"

Only if I

2

t motor (P535) is

programmed.

Warning: I2t- motor monitoring (1.3 times the rated current
reached for the time period specified in (P535))

Reduce motor load

• Increase motor speed

Pos : 424 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 003 [SK 180E . .. SK 5xxE] @ 2\ mod_1347457006237_388. doc x @ 47199 @ @ 1

C003

3.0

Overcurrent, I

2

t limit

Warning: Inverter: I

2

t limit has triggered, e.g. > 1.3 x I

n

for

60s (please also note P504)

• Continuous overload at FI output

3.1

Overcurrent, chopper I

2

t

Warning: I

2

t limit for the brake chopper has triggered, 1.3x

value attained for 60s (also note P554, if present, as well as
P555, P556, P557)

• Avoid overload of brake resistance

3.5

Torque current limit

Warning: Torque current limit reached

Check

(P112)

3.6

Current limit

Warning: Current limit reached

Check