P433
Fixed frequency 5
(Fixed frequency 5)
P
-400.0 ... 400.0 Hz
{ 0.0 }
For a description of the function of the parameter, see P429 >Fixed frequency 1<
Pos : 229 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P434 – Funkti on Digitalausg änge [ SK 54xE] @ 0\ mod_1328001103519_388.doc x @ 10227 @ @ 1
P434
[-01]
...
[-05]
Digital output function
(Digital output function)
P
0 ... 40
{ [-01] = 1 }
{ [-02] = 7 }
all other { 0 }
Up to 5 outputs (2 of which are relays) are available, which can be freely programmed with digital
functions. These can be seen in the following table.
[-01] = Output 1 / MFR1, relay output 1: External brake, (default),
terminal 1/2
[-02] = Output 2 / MFR2, relay output 2: Error, (default),
terminal 3/4
[-03] = Output 3 / DOUT1, Digital output 1: no function, (default),
terminal 5
[-04] = Output 4 / DOUT1, Digital output 2: no function, (default),
terminal 7
[-05] = Output 5 / DOUT3, Digital output 3: no function, (default),
terminal 27
a
Outputs 1 and 2 (MFR1: Control terminals 1/2 and MFR2: Control terminals 3/4): The
settings 3 to 5 and 11 work with a 10% hysteresis, i.e. the relay contact closes (Function 11
opens) when the limit value is reached and opens (function 11 closes) when a 10% smaller value
is undershot. This behaviour can be inverted with a negative value in P435.
Pos : 230 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P434 – List e der Funktionen der Rel ais- und digitalen Ausgänge @ 0\ mod_1328001177097_388. doc x @ 10250 @ 5 @ 1
List of possible functions of the relays and digital outputs
Value Function
Description
Signal*
00
No function
Input switched off.
Low
01
External brake
For the control of a mechanical brake on the motor. The relay switches at a
programmed absolute minimum frequency (P505). For typical brakes a setpoint
delay of 0.2 … 0.3 seconds should be programmed (see also P107).
A mechanical brake may be directly switched by AC current. (Note the technical
specification of the relay contacts!)
High
02
Inverter working
the closed relay contact indicates voltage at the inverter output (U - V - W) (also DC
run-
on(→ P559)).
High
03
Current limit
Based on the setting of the motor rated current in P203. This value can be adjusted
with the standardisation (P435).
High
04
Torque current limit
Based on motor data settings in P203 and P206. Signals a corresponding torque
load on the motor. This value can be adjusted with the standardisation (P435).
High
05
Frequency limit
Based on motor nominal frequency setting in P201. This value can be adjusted with
the standardisation (P435).
High
06
Setpoint reached
indicates that the FI has completed the frequency increase or decrease. Setpoint
frequency = actual frequency! From a difference of 1 Hz
à Setpoint not reached -
contact opens.
High
07
Fault
General fault message, fault is active or not yet acknowledged.
à Error – contact
opens (ready – contact closes)
Low
08
Warning
General warning - a limit value was reached that could lead to a later shutdown of
the FI.
Low
09
Overcurrent warning
At least 130% of the nominal FI current was supplied for 30 seconds.
Low
4
Digital input 7 (DIN7) can also be used as digital output 3 (DOUT3 / Binary output 5). It is recommended that either an input function (P420 [-07]
or an output function (P434 [-05]) is parameterised. However, if and input function and an output function are parameterised, a High signal from
the output function will result in the activation of the input function. This IO-exclusion is hence used as a kind of "flag". This also applies for digital
input 8 (DIN8) and digital output 2 (DOUT2 / binary output 4).