beautypg.com

P433 fixed frequency 5, P434, Digital output function – NORD Drivesystems BU0505 User Manual

Page 112

background image

SK 54xE – Users Manual for Frequency Inverters

112

BU 0505 GB-1013

P433

Fixed frequency 5

(Fixed frequency 5)

P

-400.0 ... 400.0 Hz

{ 0.0 }

For a description of the function of the parameter, see P429 >Fixed frequency 1<

Pos : 229 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P434 – Funkti on Digitalausg änge [ SK 54xE] @ 0\ mod_1328001103519_388.doc x @ 10227 @ @ 1

P434

[-01]

...

[-05]

Digital output function

(Digital output function)

P

0 ... 40

{ [-01] = 1 }

{ [-02] = 7 }

all other { 0 }

Up to 5 outputs (2 of which are relays) are available, which can be freely programmed with digital
functions. These can be seen in the following table.

[-01] = Output 1 / MFR1, relay output 1: External brake, (default),

terminal 1/2

[-02] = Output 2 / MFR2, relay output 2: Error, (default),

terminal 3/4

[-03] = Output 3 / DOUT1, Digital output 1: no function, (default),

terminal 5

[-04] = Output 4 / DOUT1, Digital output 2: no function, (default),

terminal 7

4

[-05] = Output 5 / DOUT3, Digital output 3: no function, (default),

terminal 27

a

Outputs 1 and 2 (MFR1: Control terminals 1/2 and MFR2: Control terminals 3/4): The
settings 3 to 5 and 11 work with a 10% hysteresis, i.e. the relay contact closes (Function 11
opens) when the limit value is reached and opens (function 11 closes) when a 10% smaller value
is undershot. This behaviour can be inverted with a negative value in P435.

Pos : 230 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P434 – List e der Funktionen der Rel ais- und digitalen Ausgänge @ 0\ mod_1328001177097_388. doc x @ 10250 @ 5 @ 1

List of possible functions of the relays and digital outputs

Value Function

Description

Signal*

00

No function

Input switched off.

Low

01

External brake

For the control of a mechanical brake on the motor. The relay switches at a
programmed absolute minimum frequency (P505). For typical brakes a setpoint
delay of 0.2 … 0.3 seconds should be programmed (see also P107).
A mechanical brake may be directly switched by AC current. (Note the technical
specification of the relay contacts!)

High

02

Inverter working

the closed relay contact indicates voltage at the inverter output (U - V - W) (also DC
run-

on(→ P559)).

High

03

Current limit

Based on the setting of the motor rated current in P203. This value can be adjusted
with the standardisation (P435).

High

04

Torque current limit

Based on motor data settings in P203 and P206. Signals a corresponding torque
load on the motor. This value can be adjusted with the standardisation (P435).

High

05

Frequency limit

Based on motor nominal frequency setting in P201. This value can be adjusted with
the standardisation (P435).

High

06

Setpoint reached

indicates that the FI has completed the frequency increase or decrease. Setpoint
frequency = actual frequency! From a difference of 1 Hz

à Setpoint not reached -

contact opens.

High

07

Fault

General fault message, fault is active or not yet acknowledged.

à Error – contact

opens (ready – contact closes)

Low

08

Warning

General warning - a limit value was reached that could lead to a later shutdown of
the FI.

Low

09

Overcurrent warning

At least 130% of the nominal FI current was supplied for 30 seconds.

Low

4

Digital input 7 (DIN7) can also be used as digital output 3 (DOUT3 / Binary output 5). It is recommended that either an input function (P420 [-07]

or an output function (P434 [-05]) is parameterised. However, if and input function and an output function are parameterised, a High signal from
the output function will result in the activation of the input function. This IO-exclusion is hence used as a kind of "flag". This also applies for digital
input 8 (DIN8) and digital output 2 (DOUT2 / binary output 4).