Unpacking

1. Remove the product from its packing. Retain the packing for future use, in case it is

necessary to transport the instrument to a different site or to return it to the supplier for
servicing.

2. The instrument is supplied with a panel gasket and push-fit mounting clamp. A multi-page

concise manual is supplied with the instrument, in one or more languages. Examine the
delivered items for damage or defects. If any are found, contact your supplier
immediately.

Installation

CAUTION:

Installation should be only performed by technically competent

personnel. It is the responsibility of the installing engineer to ensure that
the configuration is safe. Local Regulations regarding electrical installation
& safety must be observed (e.g. US National Electrical Code (NEC) or
Canadian Electrical Code).

Figure 1. Main dimensions

Panel-Mounting

The controller should be mounted in a properly earthed metal cabinet. The mounting panel
must be rigid and may be up to 6.0mm (0.25 inches) thick. The cut-out size is:

92mm x 92mm (+0.5mm / -0.0mm).