beautypg.com

West Control Solutions Pro-EC44 User Manual

Page 185

background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 178

LED 1 Option C Digital Indication

Bit

If bit =1, Digital Cn status is selected

Dec

7696

24080

48160

RW

0

Digital Input C1

Hex

1E10

5E10

BC20

1

Digital Input C2

2

Digital Input C3

3

Digital Input C4

4

Digital Input C5

5

Digital Input C6

6

Digital Input C7

LED 1 Control Indication

Bit

If bit =1, the function's status is selected

Dec

7644

24028

48056

RW

0

Loop 1 Auto Tune (self-tune=On, pre-tune=flashing)

Hex 1DDC 5DDC

BBB8

1

Loop 1 Manual Control

2

Loop 2 Auto Tune (self-tune=On, pre-tune=flashing)

3

Loop 2 Manual Control

LED 2 Usage

Value

LED 2 Usage. For 8 & 9 see also LED 2 Selections.

Dec

7665

24049

48098

RW

0

Loop 1 Primary Control ON = LED 1 ON

Hex

1DF1

5DF1

BBE2

1

Loop 1 Secondary Control ON = LED 1 ON

2

Loop 2 Primary Control ON = LED 1 ON

3

Loop 2 Secondary Control ON = LED 1 ON

4

Loop 1 VMD Open ON = LED 1 ON

5

Loop 1 VMD Close ON = LED 1 ON

6

Loop 2 VMD Open ON = LED 1 ON

7

Loop 2 VMD Close ON = LED 1 ON

8

Alarm/Events/Digital/Control (Logical OR of selection
below)

9

Alarm/Events/Digital/Control inverted (Logical NOR of
selection)

Value 8 (Logical OR selection of Alarm/Events/Digital/Control) turns ON the LED if any of the selected
alarms, events, inputs or functions are active.
Value 9 (Logical NOR selection of Alarm/Events/Digital/Control) turns OFF the LED if any of the selected
alarms, events, inputs or functions are active.

Note: Pre-tune will flash the LED instead of turning it on, but flashing will be obscured if used in
conjunction with other functions when they are on.

LED 2 Alarm Indication

Bit

If bit =1, Alarm n status is selected

Dec

7698

24082

48164

RW

0

Alarm 1

Hex

1E12

5E12

BC24

1

Alarm 2

2

Alarm 3

3

Alarm 4

4

Alarm 5

5

Alarm 6

6

Alarm 7