West Control Solutions Pro-EC44 User Manual
Page 177
Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-1 October 2013
Page 170
Alarm 6 Inhibit Status
Value
Alarm 6 Inhibit Status
Dec
6229
22613 45226
RO
0
Not Inhibited
Hex
1855
5855
B0AA
1
Inhibited
Alarm 6 Label
Main Language Name For Alarm 6 In Status Screen
Dec
6231
22615 45230
RW
8 ASCII characters replacing the title "Alarm 6" in alarm status
screens when main display language is used, read/written with
Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A
to Z, plus Я ц ( ) - and _.
Hex
1857
5857
B0AE
Alarm 6 Alternate Label
Alternate Language Name For Alarm 6 In Status Screen
Dec
6232
22616 45232
RW
8 ASCII characters replacing the title "Alarm 6" in alarm status
screens when the alternate language is used, read/written with
Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A
to Z, plus Я ц ( ) - and _.
Hex
1858
5858
B0B0
Alarm 6 Minimum Duration
Alarm 6 Minimum Duration
Dec
6233
22617 45234
RW
Minimum time alarm 6 must be passed its threshold before
activating (deactivation is not affected by this parameter).
From 0 to 9999 secs
Hex
1859
5859
B0B2
Alarm 7 Input Source
Value
Source
Dec
6239
22623 45246
RW
0
Input 1
Hex
185F
585F
B0BE
1
Input 2
2
Aux A Input
3
Control Loop 1 Primary Power
4
Control Loop 1 Secondary Power
5
Control Loop 2 Primary Power
6
Control Loop 2 Secondary Power
7
Loop 1
8
Loop 2
Alarm 7 Type
Value
Alarm 7 Type
Dec
6240
22624 45248
RW
0
Unused
Hex
1860
5860
B0C0
1
Process High Alarm
2
Process Low Alarm
3
Deviation Alarm (SP-PV)
4
Band Alarm
5
Input Rate of Change
6
Input/Sensor Break Alarm
7
Loop Alarm
10
% memory used
11
High Power Alarm
12
Low Power Alarm
Alarm 7 Value
Value At Which Alarm 7 Activates
Dec
6241
22625 45250
RW
Limited by input scaling for alarm types 1 to 4.
Not used for alarms 5, 6 or 7.
0 to 100% for alarms 10 to 12.
Hex
1861
5861
B0C2
Alarm 7 Rate of Change Value
Process Variable Rate of Change Alarm Threshold
Dec
6246
22630 45260
RW
Value for Rate of Change Alarm. Alarm 7 activates when PV
change exceeds this level. From 0.0 to 99999
Hex
1866
5866
B0CC
Alarm 7 Hysteresis
Alarm 7 Hysteresis Value
Dec
6242
22626 45252
RW
Deadband value (on “safe” side of alarm), through which signal
must pass before Alarm 7 deactivates.
Limited by the input scaling span
Hex
1862
5862
B0C4