beautypg.com

Output 5 parameters – West Control Solutions Pro-EC44 User Manual

Page 153

background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 146

Output 5 Parameters

Parameter Name & Register Address

Integer Int +1

Float

Access

Values

& Descriptions

Linear Output 5 Fitted

Value

Linear Output 5 Fitted

Dec

3005

19389 38778

RO

0

Not fitted

Hex

0BBD

4BBD

977A

1

Fitted

Output 5 Usage

Value

Output 5 Function

Dec

10106

26490 52980

RW

0

Disabled

Hex

277A

677A

CEF4

1

Loop 1 Primary Output Power

2

Loop 1 Secondary Output Power

3

Loop 1 VMD Open

4

Loop 1 VMD Close

5

Loop 2 Primary Output Power

6

Loop 2 Secondary Output Power

7

Loop 2 VMD Open

8

Loop 2 VMD Close

9

OR Alarm Event Direct

10

OR Alarm Event Reverse

11

AND Alarm Event Direct

12

AND Alarm Event Reverse

Output 5 Status

Value

Output 5 Status

Dec

3006

19390 38780

RO

0

Inactive

Hex

0BBE

4BBE

977C

1

Active

Digital Output 5 Latch Enable

Value

Latch Enable

Dec

3007

19391 38782

RW

0

Disable

Hex

0BBF

4BBF

977E

1

Enable

Digital Output 5 Clear Latch

Value

Latch Clear

Dec

3009

19393 38786

RW

0

Do Nothing

Hex

0BC1

4BC1

9782

1

Clear Latch

Digital Output 5 Latch State

Value

Latch State

Dec

3008

19392 38784

RO

0

Unlatched

Hex

0BC0

4BC0

9780

1

Latched

Output 5 OR Alarm Selection

Bit

If Bit = 1, Alarm n Is Included in OR Selection

Dec

10131

26515 53030

RW

2

Alarm 1

Hex

2793

6793

CF26

3

Alarm 2

4

Alarm 3

5

Alarm 4

6

Alarm 5

7

Alarm 6

8

Alarm 7

Output 5 OR Event Selection

Bit

If Bit = 1, Event n Is Included in OR Selection

Dec

10132

26516 53032

RW

2

Event 1

Hex

2794

6794

CF28

3

Event 2

4

Event 3

5

Event 4

6

Event 5

7

Profile Running

8

Profile End

This manual is related to the following products: