beautypg.com

West Control Solutions Pro-EC44 User Manual

Page 184

background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 177

LED 1 Usage

Value

LED 1 Usage. For 8 & 9 see also LED 1 Selections.

Dec

7664

24048

48096

RW

0

Loop 1 Primary Control ON = LED 1 ON

Hex

1DF0

5DF0

BBE0

1

Loop 1 Secondary Control ON = LED 1 ON

2

Loop 2 Primary Control ON = LED 1 ON

3

Loop 2 Secondary Control ON = LED 1 ON

4

Loop 1 VMD Open ON = LED 1 ON

5

Loop 1 VMD Close ON = LED 1 ON

6

Loop 2 VMD Open ON = LED 1 ON

7

Loop 2 VMD Close ON = LED 1 ON

8

Alarm/Event/Digital/Control (Logical OR)

9

Alarm/Event/Digital/Control inverted (Logical NOR)

Value 8 (Logical OR selection of Alarm/Events/Digital/Control) turns ON the LED if any of the selected
alarms, events, inputs or functions are active.
Value 9 (Logical NOR selection of Alarm/Events/Digital/Control) turns OFF the LED if any of the selected
alarms, events, inputs or functions are active.

Note: Pre-tune will flash the LED instead of turning it on, but flashing will be obscured if used in
conjunction with other functions when they are on.

LED 1 Alarm Indication

Bit

If bit =1, Alarm n status is selected

Dec

7690

24074

48148

RW

0

Alarm 1

Hex

1E0A

5E0A

BC14

1

Alarm 2

2

Alarm 3

3

Alarm 4

4

Alarm 5

5

Alarm 6

6

Alarm 7

LED 1 Profiler Event Indication

Bit

If bit =1, Event n status is selected

Dec

7692

24076

48152

RW

0

Event 1

Hex

1E0C

5E0C

BC18

1

Event 2

2

Event 3

3

Event 4

4

Event 5

5

Profile Running

6

Profile End

LED 1 Slot A & Soft Input Indication

Bit

If bit =1, Digital A / Soft Input n status is selected

Dec

7694

24078

48156

RW

0

Digital Input A

Hex

1E0E

5E0E

BC1C

1

Soft Digital 1

2

Soft Digital 2

3

Soft Digital 3

4

Soft Digital 4