beautypg.com

West Control Solutions Pro-EC44 User Manual

Page 179

background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 172

Memory Remaining

Remaining Data Recorder Capacity

Dec

7554

23938 47876

RO

The unused memory remaining, in bytes.

Hex

1D82

5D82

BB04

Time Remaining

Remaining Data Recorder Time

Dec

7555

23939 47878

RO

Approximate recording time remaining until memory filled, in

seconds. Based on the current recorder settings & sample rate.

Hex

1D83

5D83

BB06

Recorder Auto-Alarm Trigger

Value

Automatic Data Recorder Trigger

Dec

7563

23947 47894

RW

0

None

Hex

1D8B

5D8B

BB16

1

On Alarm

2

On Profile Run

3

On Alarm or Profile Running

Operator Access To Record Trigger

Value

Operator Access To Manual Record Trigger

Dec

7559

23943 47886

RW

0

No

Hex

1D87

5D87

BB0E

1

Yes

Recorder Status In Operator Mode

Value

Recorder Status Visible In Operator Mode

Dec

7560

23944 47888

RW

0

No

Hex

1D88

5D88

BB10

1

Yes

Record Input 1 Process Variable

Value

Record Process Variable Of Input 1

Dec

7572

23956 47912

RW

0

Do Not Record PV

Hex

1D94

5D94

BB28

1

Record PV Value

Record Input 1 Max Between Samples

Value

Record Max PV For Input 1 Since Last Sample

Dec

7573

23957 47914

RW

0

Do Not Record Maximum PV

Hex

1D95

5D95

BB2A

1

Record Maximum PV Between Samples

Record Input 1 Min Between Samples

Value

Record Min PV For Input 1 Since Last Sample

Dec

7574

23958 47916

RW

0

Do Not Record Minimum PV

Hex

1D96

5D96

BB2C

1

Record Minimum PV Between Samples

Record Input 2 Process Variable

Value

Record Process Variable Of Input 2

Dec

7607

23991 47982

RW

0

Do Not Record PV

Hex

1DB7

5DB7

BB6E

1

Record PV Value

Record Input 2 Max Between Samples

Value

Record Max PV For Input 2 Since Last Sample

Dec

7608

23992 47984

RW

0

Do Not Record Maximum PV

Hex

1DB8

5DB8

BB70

1

Record Maximum PV Between Samples

Record Input 2 Min Between Samples

Value

Record Min PV For Input 2 Since Last Sample

Dec

7609

23993 47986

RW

0

Do Not Record Minimum PV

Hex

1DB9

5DB9

BB72

1

Record Minimum PV Between Samples

Record Aux A Input

Value

Record Auxiliary A Input Value

Dec

7606

23990 47980

RW

0

Do Not Record Aux A

Hex

1DB6

5DB6

BB6C

1

Record Aux A Value

Record Loop 1 Actual Setpoint

Value

Record Effective Value of Loop 1 Setpoint

Dec

7575

23959 47918

RW

0

Do Not Record Setpoint

Hex

1D97

5D97

BB2E

1

Record Actual Setpoint

Record Loop 2 Actual Setpoint

Value

Record Effective Value of Loop 2 Setpoint

Dec

7610

23994 47988

RW

0

Do Not Record Setpoint

Hex

1DBA

5DBA

BB74

1

Record Actual Setpoint

This manual is related to the following products: