West Control Solutions Pro-EC44 User Manual
Page 175
Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-1 October 2013
Page 168
Alarm 5 Input Source
Value
Source
Dec
6207
22591 45182
RW
0
Input 1
Hex
183F
583F
B07E
1
Input 2
2
Aux A Input
3
Control Loop 1 Primary Power
4
Control Loop 1 Secondary Power
5
Control Loop 2 Primary Power
6
Control Loop 2 Secondary Power
7
Loop 1
8
Loop 2
Alarm 5 Type
Value
Alarm 5 Type
Dec
6208
22592 45184
RW
0
Unused
Hex
1840
5840
B080
1
Process High Alarm
2
Process Low Alarm
3
Deviation Alarm (SP-PV)
4
Band Alarm
5
Input Rate of Change
6
Input/Sensor Break Alarm
7
Loop Alarm
10
% memory used
11
High Power Alarm
12
Low Power Alarm
Alarm 5 Value
Value At Which Alarm 5 Activates
Dec
6209
22593 45186
RW
Limited by input scaling for alarm types 1 to 4.
Not used for alarms 5, 6 or 7.
0 to 100% for alarms 10 to 12.
Hex
1841
5841
B082
Alarm 5 Rate of Change Value
Process Variable Rate of Change Alarm Threshold
Dec
6214
22598 45196
RW
Value for Rate of Change Alarm. Alarm 5 activates when PV
change exceeds this level. From 0.0 to 99999
Hex
1846
5846
B08C
Alarm 5 Hysteresis
Alarm 5 Hysteresis Value
Dec
6210
22594 45188
RW
Deadband value (on
“safe” side of alarm), through which signal
must pass before Alarm 5 deactivates.
Limited by the input scaling span
Hex
1842
5842
B084
Alarm 5 Inhibit Enable/disable
Value
Alarm 5 Power-up/Setpoint Change Inhibit
Dec
6211
22595 45190
RW
0
Disabled
Hex
1843
5843
B086
1
Enabled
Alarm 5 Status
Value
Alarm 5 Status
Dec
6212
22596 45192
RO
0
Inactive
Hex
1844
5844
B088
1
Active
Alarm 5 Inhibit Status
Value
Alarm 5 Inhibit Status
Dec
6213
22597 45194
RO
0
Not Inhibited
Hex
1845
5845
B08A
1
Inhibited
Alarm 5 Label
Main Language Name For Alarm 5 In Status Screen
Dec
6215
22599 45198
RW
8 ASCII characters replacing the title "Alarm 5" in alarm status
screens when main display language is used, read/written with
Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A
to Z, plus Я ц ( ) - and _.
Hex
1847
5847
B08E