Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 190

Profile Name Character 1

A/R

A/R

The ASCII codes equivalent to each of the

16 characters of the profile name, e.g.:

A = 65dec / 0x41, B = 66dec / 0x42 etc.

a = 97dec / 0x61, b = 98dec / 0x62 etc.

Valid characters are 0 to 9, a to z, A to Z,

plus Я ц ( ) - and _.

Note: Only valid characters from the

instruments supported character set

should be used

The space character (32dec / 0x20hex) is

used to fill any unused characters at the

end of the name.

Profile Name Character 2

A/R

A/R

Profile Name Character 3

A/R

A/R

Profile Name Character 4

A/R

A/R

Profile Name Character 5

A/R

A/R

Profile Name Character 6

A/R

A/R

Profile Name Character 7

A/R

A/R

Profile Name Character 8

A/R

A/R

Profile Name Character 9

A/R

A/R

Profile Name Character 10

A/R

A/R

Profile Name Character 11

A/R

A/R

Profile Name Character 12

A/R

A/R

Profile Name Character 13

A/R

A/R

Profile Name Character 14

A/R

A/R

Profile Name Character 15

A/R

A/R

Profile Name Character 16

A/R

A/R

Profile Start Signal High Byte

0

0

0 = No delay, 1 = After delay, 2 = At
Time/day *2 only if recorder (RTC) fitted

Profile Start Signal Low Byte

A/R

A/R

Profile Start Time (Byte 4 - High)

A/R

(Floating point

number)

The time, in elapsed seconds from the start

trigger, before a profile will begin if Start

Signal =1 (After Delay) or seconds from

midnight if Start Signal =2 (Time of Day)

Use zero if Start Signal =0 (No Delay)

Profile Start Time (Byte 3)

Profile Start Time (Byte 2)

Profile Start Time (Byte 1 - Low)

Profile Start Day High Byte

0

0

1 = Monday, 2 = Tuesday, 3 = Wednesday,
4 = Thursday, 5 = Friday, 6 = Saturday, 7 =
Sunday, 8 = Monday to Friday, 9 = Monday
to Saturday, 10 = Saturday And Sunday,
11= All Week. Use 1 if no recorder fitted.

Profile Start Day Low Byte

A/R

A/R

Profile Starting Setpoint High

0

0

0 = Current Setpoint, 1 = Current Process
Variable Value

Profile Starting Setpoint Low

A/R

A/R

Profile Recovery High Byte

0

0

0 = Control to off, 1 = Restart profile, 2 =
Maintain last profile setpoint, 3 = Use
controller setpoint, 4 = Continue profile
from where it was when power failed

Profile Recovery Low Byte

A/R

A/R

Profile Recovery Time (Byte 4 - high)

A/R

(Floating point

number)

The Profile Recovery Time (before the

recovery action will be used after

power/signal returns).

Entered as elapsed seconds.
Use zero if no recorder fitted.

Profile Recovery Time (Byte 3)

Profile Recovery Time (Byte 2)

Profile Recovery Time (Byte 1 - Low)

Profile Abort action High Byte

0

0

0 = Control to off, 1 = Maintain last profile
setpoint, 2 = Use controller setpoint

Profile Abort Action Low Byte

A/R

A/R

Profile Cycles High Byte

A/R

A/R

1 to 9999 or 10,000 for “Infinite”

Profile Cycles Low Byte

A/R

A/R

Profile Number of Loops High Byte

0

0

The number of loops to be controlled by the
profile: 1 or 2

Profile Number of Loops Low Byte

A/R

A/R

CRC High Byte

A/R

A/R

CRC Low Byte

A/R

A/R

The instrument replies to this message with an Edit Response Message.