Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 186

Operator Access To Profile Control

Value

Profile Control From Operation Mode

Dec

8260

24644 49288

RW

0

Operation Mode profile control disabled

Hex

2044

6044

C088

1

Operation Mode profile control enabled

Profile Cycles Run

Profile Cycles Run Status

Dec

8247

24631 49262

RO

The Number of times the currently running profile has cycled

Hex

2037

6037

C06E

Event 1 Status

Value

Status Of Event 1

Dec

8249

24633 49266

RO

0

Event 1 Inactive

Hex

2039

6039

C072

1

Event 1 Active

Event 2 Status

Value

Status Of Event 2

Dec

8250

24634 49268

RO

0

Event 2 Inactive

Hex

203A

603A

C074

1

Event 2 Active

Event 3 Status

Value

Status Of Event 3

Dec

8251

24635 49270

RO

0

Event 3 Inactive

Hex

203B

603B

C076

1

Event 3 Active

Event 4 Status

Value

Status Of Event 4

Dec

8252

24636 49272

RO

0

Event 4 Inactive

Hex

203C

603C

C078

1

Event 4 Active

Event 5 Status

Value

Status Of Event 5

Dec

8253

24637 49274

RO

0

Event 5 Inactive

Hex

203D

603D

C07A

1

Event 5 Active

Segment Type Status

Value

The Current Running Profile Segment Type

Dec

8258

24642 49284

RO

0

No segment

Hex

2042

6042

C084

1

Setpoint ramping up

2

Step

3

Dwell

4

Held

5

Loop

6

Join

7

End

8

Setpoint ramping down

Active Profile Name

Name of Currently Selected Profile

Dec

8259

24643 49286

RO

The name of the currently selected profile

Hex

2043

6043

C086

Secondary Profile Status

Value

Secondary Profile Status of Selected Profile

Dec

8232

24616 49232

RO

0

Profile running

Hex

2028

6028

C050

1

Input sensor break

2

Profile not valid

3

Controller in manual mode

4

Profile finished and maintaining last profile setpoint

5

Profile finished with control outputs off

6

Profile control has ended. Unit is Controller Mode.

Delay time

Remaining Profile Delay Time

Dec

8233

24617 49234

RO

The current start delay time remaining in seconds, before

selected profile will begin.

Hex

2029

6029

C052