beautypg.com

Dc linear performance, Input functions, Auxiliary input – West Control Solutions Pro-EC44 User Manual

Page 254: Auxiliary input a types & ranges, Auxiliary input performance

background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 247

DC Linear Performance

Display Scaling:

Scalable from -2000 to 100000 for any DC Linear input type.

Minimum Span:

100 display units.

Decimal Point
Display:

Decimal point selectable from 0 to 3 places.

Note: Rounds to 2 places above 99.999; 1 place above 999.99 and no
decimal above 9999.9.

DC Input Multi-Point
Linearization:

Up to 15 scaling values can be defined anywhere between 0.1 and 100%
of input.

Measurement
Accuracy:

0.1% of span

1LSD (Least significant display digit).

Maximum Overload:

1A (mA input terminals), 30V (voltage input terminals) at 25°C ambient.

Sensor Break
Protection:

Applicable for 4 to 20mA, 1 to 5V and 2 to 10V ranges only.
Break detected within two seconds. Process Control outputs go to the
pre-set power value. Low and Senor Break Alarms operate.

Input Functions

Function

Input 1

Input 2

Process Control

Loop 1

Loop 2

Cascade Control

Master Loop

Slave Loop

Ratio Control

Controlled Variable

Un-controlled Variable

Remote Setpoint (RSP)

-

RSP for loop 1

Valve Position Feedback

-

Valve Position for loop 1

Note: RSP Linear inputs only, scalable between -9999 to 10000, but actual
setpoint value is kept within the setpoint limit settings.

Auxiliary Input

Auxiliary Input A Types & Ranges

Input
Type

Ranges

mA DC

0 to 20mA

4 to 20mA

V DC

0 to 5V

1 to 5V

2 to 10V

0 to 10V

Auxiliary Input Performance

Input Sampling rate:

4 samples per second.

Input Resolution:

16 bit ADC.

Input Function:

Scalable as a Remote Setpoint (RSP) between ±0.001 & ±10000
Scaled input value used for setpoint (but constrained by setpoint limits).

Measurement
Accuracy:

0.25% of input span

1LSD (Least significant display digit).

Input Resistance:

V DC:

47KΩ

mA DC:

10

Ω

Other ranges:

Greater than 10M

resistive

Input protection:

Voltage input: will withstand up to 5x input voltage overload without
damage or degradation of performance in either polarity.
Current input: will withstand 5x input current overload in reverse
direction and up to 1A in the normal direction.

This manual is related to the following products: