West Control Solutions Pro-EC44 User Manual
Page 167
Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-1 October 2013
Page 160
Pre-Tune Secondary Status
Value
Loop 2 Pre-Tune Secondary Status
Dec
4441
20825 41650
RW
0
No Additional Information
Hex
1159
5159
A2B2
1
PV within 5% (Pre-Tune cannot run)
2
Manual Control Enabled (Pre-Tune cannot run)
3
Control has On/Off element (Pre-Tune cannot run)
4
Input not valid (Pre-Tune cannot run)
5
Control Disabled (Pre-Tune cannot run)
6
Profile Running (Pre-Tune cannot run)
7
Setpoint Ramping (Pre-Tune cannot run)
Self-Tune Secondary Status
Value
Loop 2 Self-Tune Secondary Status
Dec
4442
20826 41652
RW
0
No Additional Information
Hex
115A
515A
A2B4
2
Manual Control Enabled (Self-Tune cannot run)
3
Control has On/Off element (Self-Tune cannot run)
4
Input not valid (Self-Tune cannot run)
5
Control Disabled (Self-Tune cannot run)
Loop 2 Anti Wind-up Limit
Loop 2 Anti Wind-up Limit
Dec
4491
20875 41750
RW
Power level where integral action is suspended.
Adjustable from 10.0 to 100.0% of PID power.
Hex
118B
518B
A316
Loop 2 Motor Travel Time
Loop 2 Motor Travel Time
Dec
4443
20827 41654
RW
The motor travel time (from fully open to fully closed) for 3-point
stepping VMD control. Adjustable from 5 to 300 seconds.
Hex
115B
515B
A2B6
Loop 2 Minimum Motor On Time
Loop 2 Minimum Motor On Time
Dec
4444
20828 41656
RW
Minimum drive effort to begin moving valve for 3-point stepping
VMD control. In seconds, from 0.02 to 1/10 of Motor Travel Time
Hex
115C
515C
A2B8
Loop 2 Valve Break Action
Value
Loop 2 Sensor Break Action For VMD Control
Dec
4501
20885 41770
RW
0
Close Valve Output On
Hex
1195
5195
A32A
1
Open Valve Output On
Loop 2 Minimum Valve Position
Loop 2 Minimum Valve Position
Dec
4476
20860 41720
RW
Minimum position to drive valve in VMD Mode
from the valve close limit+1% to 100.0%
Hex
117C
517C
A2F8
Loop 2 Maximum Valve Position
Loop 2 Maximum Valve Position
Dec
4477
20861 41722
RW
Maximum position to drive valve in VMD Mode.
From 0.0% to the valve open limit-1%
Hex
117D
517D
A2FA
Loop 2 PID Set Select
Value
Loop 2 PID Set Selection
Dec
4467
20851 41702
RW
0
PID Set 1
Hex
1173
5173
A2E6
1
Gain Schedule Selected by SP
2
Gain Schedule Selected by PV
3
PID Set 2
4
PID Set 3
5
PID Set 4
6
PID Set 5
PID Set 2 - Primary Prop Band
PID Set 2 Primary Proportional Band For Loop 2
Dec
4447
20831 41662
RW
Primary Proportional Band for Gain Set 2.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
115F
515F
A2BE
PID Set 2 - Secondary Prop Band
PID Set 2 Secondary Proportional Band For Loop1
Dec
4448
20832 41664
RW
Secondary Proportional Band for Gain Set 2.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
1160
5160
A2C0