beautypg.com

Digital input setup parameters – West Control Solutions Pro-EC44 User Manual

Page 129

background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 122

Input 2 Display Point 14

Multi-Point Scaling Display Value For Point 14

Dec

1157

17541 35082

RW

Value to display at multi-point scaling point 14

Valid between the scaled input lower & upper limits

Hex

0485

4485

890A

Input 2 Scale Point 15

Multi-Point Scaling Point 15

Dec

1158

17542 35084

RW

Percentage of the scaled input where multi-point scaling value

15 is applied.

0.1 to 100.0% *set to 100% ends scaling sequence at that point.

Hex

0486

4486

890C

Input 2 Display Point 15

Multi-Point Scaling Display Value For Point 15

Dec

1159

17543 35086

RW

Value to display at multi-point scaling point 15

Valid between the scaled input lower & upper limits

Hex

0487

4487

890E

User Calibration Type

Value

Calibration Type

Dec

1161

17545 35090

RW

0

None (input 2 base calibration used)

Hex

0489

4489

8912

1

Single Point Calibration

2

Two Point Calibration

User Calibration Point - Low Value

Two Point Calibration Low Point

Dec

1162

17546 35092

RW

The input value at which the Low Offset will be applied

Valid between input 2 scaled input lower & upper limits

Hex

048A

448A

8914

User Calibration Low Offset

Two Point Calibration Low Offset Value

Dec

1163

17547 35094

RW

The Low Offset value applied to the reading at the Low

Calibration Point

0.0 to 100.0%

Hex

048B

448B

8916

User Calibration Point - High Value

Two Point Calibration High Point

Dec

1164

17548 35096

RW

The input value at which the High Offset will be applied

Valid between input 2 scaled input lower & upper limits

Hex

048C

448C

8918

User Calibration High Offset

Two Point Calibration High Offset Value

Dec

1165

17549 35098

RW

The High Offset value applied to the reading at the High

Calibration Point

0.0 to 100.0%

Hex

048D

448D

891A

Digital Input Setup Parameters

Parameter Name & Register Address

Integer Int +1

Float

Access Values & Descriptions

Invert Digital Inputs

Bit

If Bit = 1, Input n is Inverted (ON becomes OFF etc)

Dec

10059

26443 52886

RW

0

Digital Input A

Hex

274B

674B

CE96

1

Digital Input C1

2

Digital Input C2

3

Digital Input C3

4

Digital Input C4

5

Digital Input C5

6

Digital Input C6

7

Digital Input C7

8

Digital Input C8

Profile Selection Type

Value

Profile Selection & Bit Pattern Format

Dec

10029

26413 52826

RW

0

None

Hex

272D

672D

CE5A

1

Binary

2

BCD

This manual is related to the following products: