West Control Solutions Pro-EC44 User Manual
Page 174
Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-1 October 2013
Page 167
Alarm 4 Type
Value
Alarm 4 Type
Dec
6192
22576 45152
RW
0
Unused
Hex
1830
5830
B060
1
Process High Alarm
2
Process Low Alarm
3
Deviation Alarm (SP-PV)
4
Band Alarm
5
Input Rate of Change
6
Input/Sensor Break Alarm
7
Loop Alarm
10
% memory used
11
High Power Alarm
12
Low Power Alarm
Alarm 4 Value
Value At Which Alarm 4 Activates
Dec
6193
22577 45154
RW
Limited by input scaling for alarm types 1 to 4.
Not used for alarms 5, 6 or 7.
0 to 100% for alarms 10 to 12.
Hex
1831
5831
B062
Alarm 4 Rate of Change Value
Process Variable Rate of Change Alarm Threshold
Dec
6198
22582 45164
RW
Value for Rate of Change Alarm. Alarm 4 activates when PV
change exceeds this level. From 0.0 to 99999
Hex
1836
5836
B06C
Alarm 4 Hysteresis
Alarm 4 Hysteresis Value
Dec
6194
22578 45156
RW
Deadband value (on
“safe” side of alarm), through which signal
must pass before Alarm 4 deactivates.
Limited by the input scaling span
Hex
1832
5832
B064
Alarm 4 Inhibit Enable/disable
Value
Alarm 4 Power-up/Setpoint Change Inhibit
Dec
6195
22579 45158
RW
0
Disabled
Hex
1833
5833
B066
1
Enabled
Alarm 4 Status
Value
Alarm 4 Status
Dec
6196
22580 45160
RO
0
Inactive
Hex
1834
5834
B068
1
Active
Alarm 4 Inhibit Status
Value
Alarm 4 Inhibit Status
Dec
6197
22581 45162
RO
0
Not Inhibited
Hex
1835
5835
B06A
1
Inhibited
Alarm 4 Label
Main Language Name For Alarm 4 In Status Screen
Dec
6199
22583 45166
RW
8 ASCII characters replacing the title "Alarm 4" in alarm status
screens when main display language is used, read/written with
Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A
to Z, plus Я ц ( ) - and _.
Hex
1837
5837
B06E
Alarm 4 Alternate Label
Alternate Language Name For Alarm 4 In Status Screen
Dec
6200
22584 45168
RW
8 ASCII characters replacing the title "Alarm 4" in alarm status
screens when the alternate language is used, read/written with
Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A
to Z, plus Я ц ( ) - and _.
Hex
1838
5838
B070
Alarm 4 Minimum Duration
Alarm 4 Minimum Duration
Dec
6201
22585 45170
RW
Minimum time alarm 4 must be passed its threshold before
activating (deactivation is not affected by this parameter).
From 0 to 9999 secs
Hex
1839
5839
B072