Power/Signal Lost Recovery Actions

If the power is cut or the input signal is lost while a profile is running, the instrument will use
the defined Profile Recovery Method once the signal / power returns. The profile recovery
method is set in the profile header.

The possible profile recovery options are explained below.

Possible Recovery Methods:

See

note

below

A

E

End the profile and maintain the setpoint value(s) from the time the power failed.

B End the profile and use Controller Setpoint value(s).
C End the profile with the Control outputs off - setpoint value replaced by “OFF”.
D Restart the profile again from the beginning.
E Continue profile from the point it had reached when the power failed

Figure 55.

End, Abort and Recovery Actions

Note: Recorder versions always use option E (Continue profile) if the

“off time” is

less than the Profile Recovery Time setting. If the

“off time” is longer, the defined

Profile Recovery Method is used.


Note: With option E, after the power returns profile bar graph resets and shows
the remaining/elapsed time for the profile only since re-starting.

Controller SP

Run
(Start-on SP)

Power off or input lost

Power / input returns

= Control Off

Planned Profile

Off Time