Read profile memory status, Read profile status – West Control Solutions Pro-EC44 User Manual
Page 209
Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-1 October 2013
Page 202
Profile Name Character 12
A/R
A/R
Profile Name Character 13
A/R
A/R
Profile Name Character 14
A/R
A/R
Profile Name Character 15
A/R
A/R
Profile Name Character 16
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
Read Profile Memory Status
This command returns the status of the profile memory used. The response to this command
is to return a table of all the profile numbers that are in use. A value of 0x00 indicates that the
profile position is free and value of 0x01 indicates that the position is used by a profile. Using
this command in conjunction with the read profile name command can be used to create a
directory of profile numbers and profile names.
Read Profile Memory Status - Request (to instrument)
Field Name
Data
Comments
Dec
Hex
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
6
6
Read Quantity Of Registers High Byte
0
0
Read Quantity Of Registers Low Byte
32
20
Write Start Address High Byte
32
20
Write Start Address Low Byte
6
6
Write Quantity Of Registers High Byte
0
0
Write Quantity Of Registers Low Byte
1
1
Byte Count
2
2
Command Code High Byte
80
50
Command Code Low Byte
83
53
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to the Read Profile Memory Status request as follows:
Read Profile Status
Read Profile Memory Status - Response (from instrument)
Field Name
Data
Comments
Dec
Hex
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
The multi read/write function
Byte Count
64
40
Profile 0 Position
0 or
1
0 or
1