Profile Name Character 12

A/R

A/R

Profile Name Character 13

A/R

A/R

Profile Name Character 14

A/R

A/R

Profile Name Character 15

A/R

A/R

Profile Name Character 16

A/R

A/R

CRC High Byte

A/R

A/R

CRC Low Byte

A/R

A/R

Read Profile Memory Status

This command returns the status of the profile memory used. The response to this command
is to return a table of all the profile numbers that are in use. A value of 0x00 indicates that the
profile position is free and value of 0x01 indicates that the position is used by a profile. Using
this command in conjunction with the read profile name command can be used to create a
directory of profile numbers and profile names.

Read Profile Memory Status - Request (to instrument)

Field Name

Data

Comments

Dec

Hex

Unit Address

A/R

A/R

The ID address of the instrument

Function Code

23

17

Requires the multi read/write function

Read Start Address High Byte

32

20

Read Start Address Low Byte

6

6

Read Quantity Of Registers High Byte

0

0

Read Quantity Of Registers Low Byte

32

20

Write Start Address High Byte

32

20

Write Start Address Low Byte

6

6

Write Quantity Of Registers High Byte

0

0

Write Quantity Of Registers Low Byte

1

1

Byte Count

2

2

Command Code High Byte

80

50

Command Code Low Byte

83

53

CRC High Byte

A/R

A/R

CRC Low Byte

A/R

A/R

The instrument replies to the Read Profile Memory Status request as follows:

Read Profile Status

Read Profile Memory Status - Response (from instrument)

Field Name

Data

Comments

Dec

Hex

Unit Address

A/R

A/R

The ID address of the instrument

Function Code

23

17

The multi read/write function

Byte Count

64

40

Profile 0 Position

0 or

1

0 or

1