beautypg.com

Plug-in module slot 3 parameters – West Control Solutions Pro-EC44 User Manual

Page 149

background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 142

Plug-in Module Slot 3 Parameters

Parameter Name & Register Address

Integer Int +1

Float

Access

Values

& Descriptions

Plug-in Module 3 Type

Value

Module Fitted In Slot 3

Dec

2192

18576 37152

RO

0

None Fitted

Hex

0890

4890

9120

1

Single Relay

2

Single SSR Driver

3

Error (invalid module for this slot)

8

Triac

9

Dual Relay

10

Dual SSR Driver

11

24VDC Transmitter PSU

255

Error (unrecognised module)

Output 3 or 3A Status

Value

Output 3 or 3A Status

Dec

2194

18578 37156

RO

0

Inactive

Hex

0892

4892

9124

1

Active

Output 3B Status

Value

Output 3B Status

Dec

2195

18579 37158

RO

0

Inactive

Hex

0893

4893

9126

1

Active

Digital Output 3 Latch Enable

Value

Output 3 or 3A Enable / Disable Latching

Dec

2197

18581 37162

RW

0

Disabled

Hex

0895

4895

912A

1

Enabled

Digital Output 3 Clear Latch

Value

Output 3 or 3A Latch Clear

Dec

2198

18582 37164

RW

0

Do Nothing

Hex

0896

4896

912C

1

Clear Latch

Digital Output 3 Latch State

Value

Output 3 or 3A Latch State

Dec

2199

18583 37166

RO

0

Unlatched

Hex

0897

4897

912E

1

Latched

Digital Output 3B Latch Enable

Value

Output 3B Enable / Disable Latching

Dec

2200

18584 37168

RW

0

Disabled

Hex

0898

4898

9130

1

Enabled

Digital Output 3B Clear Latch

Value

Output 3B Latch Clear

Dec

2201

18585 37170

RW

0

Do Nothing

Hex

0899

4899

9132

1

Clear Latch

Digital Output 3B Latch State

Value

Output 3B Latch State

Dec

2202

18586 37172

RO

0

Unlatched

Hex

089A

489A

9134

1

Latched

Output 3 Function

Value

Output 3 or 3A Function

Dec

10103

26487 52974

RW

0

Disabled

Hex

2777

6777

CEEE

1

Loop 1 Primary Output Power

2

Loop 1 Secondary Output Power

3

Loop 1 VMD Open

4

Loop 1 VMD Close

5

Loop 2 Primary Output Power

6

Loop 2 Secondary Output Power

7

Loop 2 VMD Open

8

Loop 2 VMD Close

9

OR Alarm Event Direct

This manual is related to the following products: