Isolation:

Reinforced safety isolation from outputs and inputs

Sensor Break
Detection:

Applicable for 4 to 20mA, 1 to 5V and 2 to 10V ranges only.
Control goes to the pre-set power value if Auxiliary Input is providing the
active setpoint source.

Digital Inputs

Digital Input Functions

Function

Logic High*

Logic Low*

┌ ┐ Loop 1 Control Select

Enabled

Disabled

┌ ┐ Loop 2 Control Select

Enabled

Disabled

┌ ┐ Loop 1 Auto/Manual Select

Automatic

Manual

┌ ┐ Loop 2 Auto/Manual Select

Automatic

Manual

┌ ┐ Loop 1 Setpoint Select

Main SP

Alternate SP

┌ ┐ Loop 2 Setpoint Select

Main SP

Alternate SP

┌ ┐ Loop 1 Pre-Tune Select

Stop

Run

┌ ┐ Loop 2 Pre-Tune Select

Stop

Run

┌ ┐ Loop 1 Self-Tune Select

Stop

Run

┌ ┐ Loop 2 Self-Tune Select

Stop

Run

┌ ┐ Profile Run/Hold

Hold

Run

┌ ┐ Profile Hold Segment Release

No Action

Release

Profile Abort

No Action

Abort

Data Recorder Trigger

Not Active

Active

Output n Forcing Open/Close

Off/Open

On/Closed

Clear All Latched Outputs

No Action

Reset

Output n Clear Latch

No Action

Reset

Key n Mimic (for L D U R)

No Action

Key Pressed

Inputs C1-C7 can be used as
Binary or BCD Profile Selection

Binary 0

Binary 1

Note: The above actions apply when a digital input is setup to control the
specified function(s)
, *but the High/Low function can be switched using the Inputs
to Invert selection screen.

Digital Input Performance

Number Available

0 to 9. One from Module Slot A, 8 from Multi-Digital Input C

Type:

Voltage-free or TTL-compatible voltage signals.
Held in High state via pull-up resistors.

Logic States:

Logic High = Open contacts (>5000

Ω) or 2 to 24VDC signal.

Logic Low = Closed contacts (<50

Ω) or -0.6 to +0.8VDC signal.

*Inverted Logic:

Inputs can be inverted. This swaps the actions listed above (e.g.
Profile Aborts on Logic High if selected input is inverted).

Digital Input Sensitivity:

Inputs set for: Control disable; Auto/Manual; Setpoint Select; Pre-
Tune; Self-Tune; Profile Run/Hold and Profile Hold Segment
Release are all Edge Sensitive, where a High-Low or Low-High
transition changes the function status. Pre-Tune is always off at
power on (except if using the auto pre-tune feature), but others
functions retain their power off status at power on.
Inputs set for: Profile Abort; Data Recorder Trigger; Output Forcing;
Clearing Latched Outputs; Key Mimic and Profile Selection are all
Level Sensitive, where a high or low input sets the function status.
Digital inputs generally work in parallel with equivalent menus,
where either can change the function status.

Response Time:

Response within <0.25 second of signal state change.

Isolation:

Reinforced safety isolation from inputs and outputs.