beautypg.com

West Control Solutions Pro-EC44 User Manual

Page 161

background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 154

Loop 1 Combined Power

Loop 1 Combined Primary & Secondary Power Level

Dec

4331

20715 41430

RO

The current loop 1 combined PID power level (-100 to 100%)

Hex

10EB

50EB

A1D6

Loop 1 Pre-Tune Status

Value

Pre-Tune Status For Loop 1

Dec

4332

20716 41432

RO

0

Inactive

Hex

10EC

50EC

A1D8

1

Active

Loop 1 Self-Tune Status

Value

Self-Tune Status For Loop 1

Dec

4333

20717 41434

RO

0

Inactive

Hex

10ED

50ED

A1DA

1

Active

Loop 1 Loop Alarm status

Value

Loop Alarm Status For Loop 1

Dec

4334

20718 41436

RO

0

Inactive

Hex

10EE

50EE

A1DC

1

Active

Loop 1 Input Failure Pre-set Power

Loop 1 Input Sensor Break Pre-set Power

Dec

4335

20719 41438

RW

The pre-defined power output applied if input signal is lost

0 to 100% (-100% to 100% for dual control).

Hex

10EF

50EF

A1DE

Loop 1 Auto Pre-tune

Value

Auto Pre-Tune At Every Power-up For Loop 1

Dec

4336

20720 41440

RW

0

Disabled

Hex

10F0

50F0

A1E0

1

Enabled

Pre-tune Secondary Status

Value

Pre-tune Secondary Status

Dec

4341

20725 41450

RO

0

No Additional Information

Hex

10F5

50F5

A1EA

1

PV within 5% (Pre-Tune cannot run)

2

Manual Control Enabled (Pre-Tune cannot run)

3

Control has On/Off element (Pre-Tune cannot run)

4

Input not valid (Pre-Tune cannot run)

5

Control Disabled (Pre-Tune cannot run)

6

Profile Running (Pre-Tune cannot run)

7

Setpoint Ramping (Pre-Tune cannot run)

Self-tune Secondary Status

Value

Self-tune Secondary Status

Dec

4342

20726 41452

RO

0

No Additional Information

Hex

10F6

50F6

A1EC

2

Manual Control Enabled (Self-Tune cannot run)

3

Control has On/Off element (Self-Tune cannot run)

4

Input not valid (Self-Tune cannot run)

5

Control Disabled (Self-Tune cannot run)

Loop 1 Anti Wind-up Limit

Loop 1 Anti Wind-up Limit

Dec

4391

20775 41550

RW

Power level where integral action is suspended.

Adjustable from 10.0 to 100.0% of PID power.

Hex

1127

5127

A24E

Loop 1 Motor Travel Time

Loop 1 Motor Travel Time

Dec

4343

20727 41454

RW

The motor travel time (from fully open to fully closed) for 3-point

stepping VMD control. Adjustable from 5 to 300 seconds.

Hex

10F7

50F7

A1EE

Loop 1 Minimum Motor On Time

Loop 1 Minimum Motor On Time

Dec

4344

20728 41456

RW

Minimum drive effort to begin moving valve for 3-point stepping

VMD control. In seconds, from 0.02 to 1/10 of Motor Travel Time

Hex

10F8

50F8

A1F0

Loop 1 VMD Break Action

Value

Loop 1 Sensor Break Action For VMD Control

Dec

4401

20785 41570

RW

0

Close Valve Output On

Hex

1131

5131

A262

1

Open Valve Output On

Loop 1 Valve Close Limit

Loop 1 Minimum Valve Position

Dec

4376

20760 41520

RW

Minimum position to drive valve in VMD Mode

from the valve close limit+1% to 100.0%

Hex

1118

5118

A230

This manual is related to the following products: