Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 166

Alarm 3 Value

Value At Which Alarm 3 Activates

Dec

6177

22561 45122

RW

Limited by input scaling for alarm types 1 to 4.

Not used for alarms 5, 6 or 7.

0 to 100% for alarms 10 to 12.

Hex

1821

5821

B042

Alarm 3 Rate of Change Value

Process Variable Rate of Change Alarm Threshold

Dec

6182

22566 45132

RW

Value for Rate of Change Alarm. Alarm 3 activates when PV

change exceeds this level. From 0.0 to 99999

Hex

1826

5826

B04C

Alarm 3 Hysteresis

Alarm 3 Hysteresis Value

Dec

6178

22562 45124

RW

Deadband value (on

“safe” side of alarm), through which signal

must pass before Alarm 3 deactivates.

Limited by the input scaling span

Hex

1822

5822

B044

Alarm 3 Inhibit Enable/disable

Value

Alarm 3 Power-up/Setpoint Change Inhibit

Dec

6179

22563 45126

RW

0

Disabled

Hex

1823

5823

B046

1

Enabled

Alarm 3 Status

Value

Alarm 3 Status

Dec

6180

22564 45128

RO

0

Inactive

Hex

1824

5824

B048

1

Active

Alarm 3 Inhibit Status

Value

Alarm 3 Inhibit Status

Dec

6181

22565 45130

RO

0

Not Inhibited

Hex

1825

5825

B04A

1

Inhibited

Alarm 3 Label

Main Language Name For Alarm 3 In Status Screen

Dec

6183

22567 45134

RW

8 ASCII characters replacing the title "Alarm 3" in alarm status

screens when main display language is used, read/written with

Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A

to Z, plus Я ц ( ) - and _.

Hex

1827

5827

B04E

Alarm 3 Alternate Label

Alternate Language Name For Alarm 3 In Status Screen

Dec

6184

22568 45136

RW

8 ASCII characters replacing the title "Alarm 3" in alarm status

screens when the alternate language is used, read/written with

Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A

to Z, plus Я ц ( ) - and _.

Hex

1828

5828

B050

Alarm 3 Minimum Duration

Alarm 3 Minimum Duration

Dec

6185

22569 45138

RW

Minimum time alarm 3 must be passed its threshold before

activating (deactivation is not affected by this parameter).

From 0 to 9999 secs

Hex

1829

5829

B052

Alarm 4 Input Source

Value

Source

Dec

6191

22575 45150

RW

0

Input 1

Hex

182F

582F

B05E

1

Input 2

2

Aux A Input

3

Control Loop 1 Primary Power

4

Control Loop 1 Secondary Power

5

Control Loop 2 Primary Power

6

Control Loop 2 Secondary Power

7

Loop 1

8

Loop 2