Recorder & clock parameters – West Control Solutions Pro-EC44 User Manual
Page 178
Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-1 October 2013
Page 171
Alarm 7 Inhibit Enable/disable
Value
Alarm 7 Power-up/Setpoint Change Inhibit
Dec
6243
22627 45254
RW
0
Disabled
Hex
1863
5863
B0C6
1
Enabled
Alarm 7 Status
Value
Alarm 7 Status
Dec
6244
22628 45256
RO
0
Inactive
Hex
1864
5864
B0C8
1
Active
Alarm 7 Inhibit Status
Value
Alarm 7 Inhibit Status
Dec
6245
22629 45258
RO
0
Not Inhibited
Hex
1865
5865
B0CA
1
Inhibited
Alarm 7 Label
Main Language Name For Alarm 7 In Status Screen
Dec
6247
22631 45262
RW
8 ASCII characters replacing the title "Alarm 7" in alarm status
screens when main display language is used, read/written with
Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A
to Z, plus Я ц ( ) - and _.
Hex
1867
5867
B0CE
Alarm 7 Alternate Label
Alternate Language Name For Alarm 7 In Status Screen
Dec
6248
22632 45264
RW
8 ASCII characters replacing the title "Alarm 7" in alarm status
screens when the alternate language is used, read/written with
Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A
to Z, plus Я ц ( ) - and _.
Hex
1868
5868
B0D0
Alarm 7 Minimum Duration
Alarm 7 Minimum Duration
Dec
6249
22633 45266
RW
Minimum time alarm 7 must be passed its threshold before
activating (deactivation is not affected by this parameter).
From 0 to 9999 secs
Hex
1869
5869
B0D2
Recorder & Clock Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Descriptions
Recording Sample Interval
Value
Recording Sample Interval
Dec
7550
23934 47868
RW
0
Every Second
Hex
1D7E
5D7E
BAFC
1
Every 2 Seconds
2
Every 5 Seconds
3
Every 10 Seconds
4
Every 15 Seconds
5
Every 30 Seconds
6
Every Minute
7
Every 2 Minutes
8
Every 5 Minutes
9
Every 10 Minutes
10
Every 15 Minutes
11
Every 30 Minutes
Recording Mode
Value
Recording Mode
Dec
7551
23935 47870
RW
0
Record until memory used
Hex
1D7F
5D7F
BAFE
1
Continuous FIFO buffer
Manual Recording Trigger
Value
Manual Recording Trigger
Dec
7552
23936 47872
RW
0
Manual Recording Trigger Off
Hex
1D80
5D80
BB00
1
Manual Recording Trigger On
Data Recorder Fitted
Value
Data Recorder Fitted
Dec
7553
23937 47874
RO
0
Not Fitted
Hex
1D81
5D81
BB02
1
Recorder Fitted