beautypg.com

Profile end actions – West Control Solutions Pro-EC44 User Manual

Page 101

background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 94

Profile End Actions

Once a running profile ends, that profiles’ Segment End Type defines the action taken by
the instrument. If a sequence of profiles are joined together, the End Segment Type of the
last profile in the sequence will be carried out when it completes. The end segment type is
set in the final profile segment data.


The possible profile end actions are explained below.

Possible Profile End Actions:

See

note

below

C

A

E

At profile end, maintain the Final Setpoint value(s) of the last segment.

B At profile end, exit Profiler Mode and use the Controller Setpoint value(s).
C At profile end, remain in Profiler Mode with the Control outputs off.

Figure 56.

Profile End Action

Note: Note: When using two loop profiles, the end-action applies to both loops,
but each ends with its own individual setpoint in line with the method chosen.

Controller SP

Run
(Start-on SP)

Normal Profile End

= Control Off

Last Profile SP

Controller SP

This manual is related to the following products: