beautypg.com

6 messages & error indications, Plug-in module problems, Sensor break detection – West Control Solutions Pro-EC44 User Manual

Page 38: Un-calibrated input detection, Pv over-range or under-range indication, Messages & error indications

background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 31

6 Messages & Error Indications

Plug-in Module Problems

If an invalid or unknown module is detected in one of the plug-in module slots during the
power-up self-test, the message

Fault Found, Press R, for details” is shown. This is

followed by

Replace faulty module in Module Slot n, Press R,” (where n is the faulty slot

location). The Service Contact information is displayed next showing details of who to
contact if a fault persists

Replace the module in slot “n”. If this does not solve the problem, return the instrument for
investigation.

CAUTION:

Do not continue using the product until the the error is resolved.

Sensor Break Detection

Whenever a problem is detected with a process variable or auxiliary input connection, the
displayed value for that input

is replaced with the word “OPEN”; except in Ratio control

where an open input 1 or 2 is shown as “x1-Open” or “x2-Open”. See Redundant Input
(page 83) to protect critical processes from sensor faults.

This may be the result of a failed sensor, a broken connection or an input circuit fault.
In this condition, the control outputs go to the pre-set power value (see Control Configuration
– page 50).

CAUTION:

Correct the signal/wiring problem to continue normal operation.

Un-Calibrated Input Detection

The instrument is fully calibrated during manufacture. If a fault occurs and calibration data is
lost, the process input displays are

replaced with the word “ERROR” and error is shown

instead of “Calibrated” for effected inputs in Service & Product Information mode.
In this condition, the control outputs go to the pre-set power value (see Control Configuration
– page 50).

CAUTION:

Perform a full base calibration of the input before continuing

normal operation (see page 72). If the problem persists, return the
instrument for servicing.

PV Over-range or Under-range Indication

If a measured process input value is more than 5% above than the Scaled Input Upper Limit,
its value is replace by the word “HIGH” to indicate that it is out of range.

If a measured process input value is more than 5% below than the Scaled Input Lower Limit,
its value is replaced

by the word “LOW” to indicate that it is out of range.

This manual is related to the following products: