West Control Solutions Pro-EC44 User Manual
Page 162
Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-1 October 2013
Page 155
Loop 1 Valve Open Limit
Loop 1 Maximum Valve Position
Dec
4377
20761 41522
RW
Maximum position to drive valve in VMD Mode.
From 0.0% to the valve open limit-1%
Hex
1119
5119
A232
Loop 1 PID Set Select
Value
Loop 1 PID Set Selection
Dec
4367
20751 41502
RW
0
PID Set 1
Hex
110F
510F
A21E
1
Gain Schedule Selected by SP
2
Gain Schedule Selected by PV
3
PID Set 2
4
PID Set 3
5
PID Set 4
6
PID Set 5
PID Set 2 - Primary Prop Band
PID Set 2 Primary Proportional Band For Loop 1
Dec
4347
20731 41462
RW
Primary Proportional Band for Gain Set 2.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
10FB
50FB
A1F6
PID Set 2 - Secondary Prop Band
PID Set 2 Secondary Proportional Band For Loop1
Dec
4348
20732 41464
RW
Secondary Proportional Band for Gain Set 2.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
10FC
50FC
A1F8
PID Set 2 - Integral Time
PID Set 2 - Integral Time For Loop 1
Dec
4349
20733 41466
RW
Gain Set 2 integral time constant for loop 1
0.1 to 5999 Seconds. 0 or 6000 = OFF
Hex
10FD
50FD
A1FA
PID Set 2 - Derivative Time
PID Set 2 - Derivative Time For Loop 1
Dec
4350
20734 41468
RW
Gain Set 2 derivative time constant for loop 1
0.1 to 5999 Seconds. 0 or 6000 = OFF
Hex
10FE
50FE
A1FC
PID Set 2 - Overlap/Deadband
PID Set 2 - Overlap/Deadband For Loop 1
Dec
4351
20735 41470
RW
PID Set 2 overlap (+ve) or deadband (-ve) between primary &
secondary prop bands. In display units - limited to 20% of the
combined band width.
Hex
10FF
50FF
A1FE
PID Set 2 - On/Off Differential
PID Set 2 - On/Off Differential For Loop 1
Dec
4378
20762 41524
RW
The on-off control hysteresis (deadband) for PID Set 2.
1 to 300 display units, centred about the setpoint.
Hex
111A
511A
A234
PID Set 3 - Primary Prop Band
PID Set 3 Primary Proportional Band For Loop 1
Dec
4352
20736 41472
RW
Primary Proportional Band for Gain Set 3.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
1100
5100
A200
PID Set 3 - Secondary Prop Band
PID Set 3 Secondary Proportional Band For Loop 1
Dec
4353
20737 41474
RW
Secondary Proportional Band for Gain Set 3.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
1101
5101
A202
PID Set 3 - Integral Time
PID Set 3 - Integral Time For Loop 1
Dec
4354
20738 41476
RW
Gain Set 3 integral time constant for loop 1
0.1 to 5999 Seconds. 0 or 6000 = OFF
Hex
1102
5102
A204
PID Set 3 - Derivative Time
PID Set 3 - Derivative Time For Loop 1
Dec
4355
20739 41478
RW
Gain Set 3 derivative time constant for loop 1
0.1 to 5999 Seconds. 0 or 6000 = OFF
Hex
1103
5103
A206
PID Set 3 - Overlap/Deadband
PID Set 3 - Overlap/Deadband For Loop 1
Dec
4356
20740 41480
RW
PID Set 3 overlap (+ve) or deadband (-ve) between primary &
secondary prop bands. In display units - limited to 20% of the
combined band width.
Hex
1104
5104
A208