Troubleshooting schedules, Error, warning and event messages, Tamper states – Interlogix TruPortal User Manual
Page 112: Power and battery events, Backup battery events
Troubleshooting
100
TruPortal Software User Guide
Troubleshooting Schedules
If a schedule is not behaving as expected, review the following sections:
•
•
•
Considerations for Schedule-Based Action Trigger Records
Error, Warning and Event Messages
Tamper States
The System Controller does not distinguish which of the four door input are in tamper state when it
logs tamper events. The real-time state of inputs in tamper can be viewed on the Monitoring >
Diagnostics page.
Power and Battery Events
System Controller Shuts Down on Battery Power
If the System Controller is operating on battery power only and the battery voltage drops below 10.2
volts, the System Controller will shut down until AC power is restored.
Backup Battery Events
Backup Battery Events occur when the backup battery voltage drops below certain thresholds.
Note:
If the System Controller is powered exclusively off of a backup battery, it will shutdown
at 10.2V and the Cutoff and Not Detected events will not be generated.
Memory Battery Event
Event Code
Event Description
Cause
Event 14612
Backup Battery Critical
Voltage falls below 11.4V, or rises above 10.2V
Event 14613
Backup Battery Cutoff
Voltage falls below 10.2V, or rises above 9.0V
Event 14624
Backup Battery Low
Voltage falls below 11.7V, or rises above 11.4V
Event 14625
Backup Battery Restored
Voltage rises above 11.7V
Event 14649
Backup Battery Not Detected
Voltage falls below 9.0V
Event Code
Event Description
Event 14618
Memory Backup Battery Low