8 Fully-closed Loop Control

8.3.6 Alarm Detection

8-22

Setting Example

If the servomotor moves 0.2

μm for every pulse of position reference, the external encoder sine wave pitch is

20

μm, and the number of divisions is 256, the electronic gear ratio will be as follow.

.

Therefore, set 512 for Pn20E (numerator B) and 200 for Pn210 (denominator A).

8.3.6 Alarm Detection

The setting of alarm detection (Pn51B/Pn52A) is shown below.

(1) Excessive Error Level between Servomotor and Load Positions (Pn51B)

This setting detects the difference between the feedback position of the motor encoder and the feedback load

position of the external encoder in fully-closed loop control. If the detected difference is above the set level,

the motor-load position error overflow alarm (A.d10) will be output.

Note: When Pn51B is set to 0, the motor-load position error overflow alarm (A.d10) is not detected.

(2) Multiplier per One Fully-closed Rotation (Pn52A)

The coefficient of the error between the external encoder and the motor per motor rotation can be set. This

function can be used to prevent the motor from running out of control due to damage to the external encoder or

to detect slippage of the belt.

Setting Example

Increase the value if the belt slips or is twisted excessively.

If the set value is 0, the external encoder value will be read as it is.

If the factory setting of 20 is used, the second rotation will start with the error for the first motor rotation mul-

tiplied by 0.8. (Refer to the following figure.)

Related Parameter

A

B

Pn210

Pn20E

20

0.2

× 256

200

512

=

=

=

=

Electronic gear ratio

Pn51B

Excessive Error Level between Servomotor and

Load Positions

Classifica-

tion

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 1073741824

1 reference unit

1000

Immediately

Setup

Position

Pn52A=0

Pn52A=100

Pn52A=20

1st

rotation

2nd

rotation

Number of motor rotations

Error between motor and external encoder

3rd

rotation

Less than

one rotation

Small

Big

Rotation

Pn52A

Multiplier per One Fully-closed Rotation

Classifica-

tion

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 100

1%

20

Immediately

Setup

Position