4.2.9 Instantaneous Power Interruption Settings
4-20
4.2.9 Instantaneous Power Interruption Settings
Determines whether to continue operation or turn the servomotor’s power OFF when the power supply voltage
is interrupted.
If the power interruption time is shorter than the set value in Pn509, the servomotor will continue operation. If
it is longer than the set value, the servomotor’s power will be turned OFF during the power interruption. The
servomotor is turned ON when power supply to the main circuit recovers.
Note: If the instantaneous power interruption is longer than the set value of Pn509, the /S-RDY signal turns OFF.
If the uninterruptible power supplies are used for the control power supply and main circuit power supply, the
SERVOPACK can withstand an instantaneous power interruption period in excess of 1000 ms.
Pn509
Instantaneous Power Cut Hold Time
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
20 to 1000
1 ms
20
Immediately
Setup
• The holding time of the control power supply for the 200 V SERVOPACK is approxi-
mately 100 ms, but the time of the control power supply for the 100 V SERVOPACKs
is approximately 65 ms. If the control power supply makes control impossible during
an instantaneous power interruption, the same operation will be performed as for nor-
mally turning OFF the power supply, and the setting of the parameter will be ignored.
• The holding time of the main circuit power supply varies with the output of the SER-
VOPACK. If the load on the servomotor is large and an undervoltage alarm (A.410)
occurs, the parameter will be ignored.
• The holding time of the control power supply (24 VDC) for the 400 V SERVOPACKs
depends on the capability of the power supply (not included). Check the power supply
before using the application.
Speed
Position
Torque
Instantaneous power interruption
Set value for Pn509
≥ OFF time (t)
OFF time (t)
Power OFF
Set value for
Pn509
≥ OFF time (t)
Set value for Pn509 <
OFF time (t)
Main circuit
power supply
Set value for
Pn509
Servomotor
status
Power ON
Instantaneous power interruption
Set value for Pn509 < OFF time (t)
Forced
OFF.
OFF time (t)
Main circuit
power supply
Set value for
Pn509
Servomotor
status
Power ON
Operation
continues.
Depends on the functions of
the command option module.