Yaskawa Sigma-5 User Manual: Design and Maintenance - Rotary Motors User Manual
Page 180

5.6 Anti-resonance Control Adjustment Function (Fn204)
5-43
Adjustments
(2) With Determined Vibration Frequency Before Adjusting the Anti-resonance Control
Step
Display after Operation
Keys
Operation
1
Press the
Key to view the main menu for the
utility function mode.
Use the
or
Key to move through the list,
select Fn204.
2
Press the
Key to display the initial setting screen
for tuning mode.
Note: If the display does not switch and “NO-OP” is
displayed, take corrective action after checking
the items given in 5.6.1 (1) Before Performing
Anti-Resonance Control Adjustment Function.
3
Press the
or
Key and select the tuning mode
“1”.
4
Press the
Key while “Tuning Mode = 1" is dis-
played. The screen shown on the left will appear and
“freq” will blink.
Waveform
5
Move the cursor with the
or
Keys and press
the
or
Keys to adjust the frequency.
6
Press the
Key. The cursor will move to “damp”.