19. Service

19.1

Cleaning

The exterior of the power source or the PACS unit may be cleaned with a cloth dampened with a
mild detergent and wrung out. Disconnect mains power before cleaning. Do not spray water or
other cleaning agents directly at the equipment.

19.2

General

This section describes the suggested maintenance and troubleshooting procedure. The
troubleshooting procedure is divided into two sections. The first section deals with basic operation
and connection of the equipment. The second section requires opening the PACS unit and using
the Test Points and a simple Digital Multimeter to troubleshoot the unit down to the circuit level.
Only a qualified electronic technician should attempt this level of troubleshooting.

CAUTION:

VOLTAGES UP TO 312 VAC MAY BE PRESENT IN CERTAIN SECTIONS OF THE

PACS MEASUREMENT UNIT.

WARNING:

THIS EQUIPMENT CONTAINS POTENTIALLY LETHAL VOLTAGES. DEATH ON

CONTACT MAY RESULT IF PERSONNEL FAIL TO OBSERVE SAFETY PRECAUTIONS. DO NOT
TOUCH ELECTRONIC CIRCUITS WHEN POWER IS APPLIED

19.3

Basic Operation

19.3.1 No Power To EUT

CONDITION

POSSIBLE CAUSE, REMEDY

No power to EUT

Line voltage or power source not at expected
value. Verify power line voltage is correct. Verify
power source voltage is at programmed value

AC source voltage OK.
No power to EUT.

Incorrect input wiring at TB4. Check for wrong
terminals or poor connections.

AC source voltage OK.
Input wiring is OK.
Still no power to EUT

Incorrect output wiring from TB3. Defective plug
and cable from front panel outlet on PACS 1.
Check output wiring from TB3, or, verify cable and
plug going to EUT is good